LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 26

Advertising
background image

LAARS Heating Systems

Page 24

Pennant 200, 300, 400

Page 25

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made in the field

wiring terminal strip, which is located to the left of the

blower.

NOTE: All internal electrical components have been

pre-wired. No attempt should be made to connect

electrical wires to any other location except the

wiring box.

5.1 Main Power

Connect a 15 amp. fused, 120-volt supply to the

main power switch (hot leg is connected directly to

switch). Neutral leg is connected directly to the white

wire. Ground wire can be connected to the grounding

screw in the box or on the switch.

Wiring diagrams are shown in Figures 13 and 14.

5.2 Field Wiring

Terminal strips are supplied for field wiring

connections under the flip-up control panel.

Connections must be made as specified by the

Connection Diagram (Figure 13). The following may

be connected to the terminal strips as field wiring:

Temperature Sensor

: The sensor supplied loose

with the Pennant is installed in the piping or tank, per

the suggested piping diagrams. The sensor, Thermistor

2, is connected to the “9” and “10” terminals.

Field Installed Pump

: A pump contactor can be

wired to the “P1” and “P2” terminals. These terminals

are attached to dry contacts of an adjustable delay

on break relay. The contacts may be used to switch a

larger pump contactor or can be used to directly switch

the hot leg of a circulator pump, up to 1hp at 120 VAC

or 3/4hp at 240 VAC.

Note that in some cases, the pump is run

continuously.

External Alarm

: An external power supply and

alarm can be connected to the “1” and “2” terminals.

In the event of an ignition time out, a contact closure

occurs across these terminals.

BAS Connections

: To use an external control

to call Pennant units for heat, connect to terminals

"3" and "4". Then put the Local/Remote Switch in the

"Remote" mode.

Other Field Interlocks

: To install other field-

wired switches (proving switches, flow switches, etc.),

remove the jumper between the terminals labeled “7”

and “8”.

Auxiliary Contacts

: The contacts between

terminals “11” and “12” will close whenever Loop 2

is enabled and there is a call for heat on Loop 2. Use

these terminals to enable field devices under these

circumstances

SECTION 6.

Operating Instructions

6.1 Filling the Boiler System

1. Ensure the system is fully connected. Close all

bleeding devices and open make-up water valve.

Allow system to fill slowly.

2. If make-up water pump is employed, adjust

pressure switch on pumping system to provide

a minimum of 12 psi (81.8 kPa) at the highest

point in the heating loop.

3. If a water pressure regulator is provided on the

make-up water line, adjust the pressure regulator

to provide at least 12 psi (81.8 kPa) at the highest

point in the heating loop.

4. Open bleeding devices on all radiation units

at the high points in the piping throughout

the system, unless automatic air bleeders are

provided at such points.

5. Run system circulating pump for a minimum of

30 minutes with the boiler shut off.

6. Open all strainers in the circulating system,

check flow switch operation, and check for

debris. If debris is present, clean out to ensure

proper circulation.

7. Recheck all air bleeders as described in Step 4.

8. Check liquid level in expansion tank. With the

system full of water and under normal operating

pressure, the level of water in the expansion tank

should not exceed 1⁄4 of the total, with the balance

filled with air.

9. Start up boiler according to the procedure in this

manual. Operate the entire system, including the

pump, boiler, and radiation units for one (1) hour.

10. Recheck the water level in the expansion tank. If

the water level exceeds 1⁄4 of the volume of the

expansion tank, open the tank drain, and drain to

that level.

11. Shut down the entire system and vent all

radiation units and high points in the system

piping, as described in Step 4.

12. Close make-up water valve and check strainer in

pressure reducing valve for sediment or debris

from the make-up water line. Reopen make-up

water valve.

13. Check gauge for correct water pressure and also

check water level in the system. If the height

indicated above the boiler insures that water is at

the highest point in the circulating loop, then the

system is ready for operation.

14. Refer to local codes and the make-up water

valve manufacturer’s instructions as to whether

the make-up water valve should be left open or

closed.

Advertising
This manual is related to the following products: