LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 8

Advertising
background image

LAARS Heating Systems

Page 6

Pennant 200, 300, 400

Page 7

The dimensions and requirements that are shown

in Table 2 should be met when choosing the locations

for the appliance.

1.6 Locating Pump-Mounted Water Heater

with Respect to Storage Tank(s)

For best results, a pump-mounted Pennant water

heater should be located within 15 feet (4.6m) of the

storage tank(s). The pump is sized for 30 feet (9.1m)

of piping.

If the appliance must be installed with longer

piping runs, then larger diameter pipe or tubing may be

acceptable. Consult the factory for assistance.

1.7 Locating Pump-Mounted Boiler with

Respect to Return/Supply Header

For the best results, a pump-mounted Pennant

boiler should be located within 15 feet (4.6m) of the

supply and return headers. The pump is sized for 30

feet (9.1m) of piping.

If the appliance must be installed with longer

piping runs, then larger diameter tubing may be

acceptable. Consult the factory for assistance.

Heater

Size

Vent Collar

Size

Horizontal

Vent Pipe

Diameter

Intake

Air Collar

& Pipe

Diameter

Max. Pipe

Length

Max. No.

of Elbows

Side Vent

Terminal

Part Number

Side Wall

Combustion

Air Terminal

Part Number

in

cm

in

cm

in

cm

ft

m

200

5

13

4

10

4

10

50

15

3

CA003101

CA003201

300

6

15

5

13

4

10

50

15

3

CA003102

CA003201

400

7

18

6

15

6

15

50

15

3

CA003103

CA003202

Table 1. Horizontal Vent / Combustion Air Parameters.

Appliance

Surface

Required

Clearance From

Combustible Material

Recommended

Service Access

Clearance

inches

cm

inches

cm

Left Side

1

2.5

24

61

Right Side

1

2.5

24

61

Top

1

2.5

12

30

Back

1

2.5

12**

30**

Front

1

2.5

36

91

Vertical

(Category 1)

Vent

6*

15.2*

Horizontal

(Category 3)

Vent

per UL 1738 venting

system supplier's

instructions

*1" (2.5 cm) when b-vent is used.

**When vent and/or combustion air connects to the back,

recommended clearance is 36" (91cm).

Table 2. Clearances.

1.8 Locating Appliance for Correct

Horizontal Vent/Ducted Air Distance

From Outside Wall

The forced draft combustion air blower in the

appliance has sufficient power to pull air and vent

properly when the guidelines for horizontal air and

vent are followed (see Table 1).

NOTE: On some models, the vent collar size is

larger than the size of the vent pipe that can be

used. Vent collar size and horizontal pipe diameters

can be found in Table 1. The larger vent collar

size is to accommodate Category I (vertical) vent

systems.
NOTE: When located on the same wall, the

Pennant combustion air intake terminal must

be installed a minimum of 12" (30cm) below the

exhaust vent terminal and separated by a minimum

of 36 inches (91cm) horizontally.

The air intake terminal must be installed high

enough to avoid blockage from snow, leaves and other

debris.

SECTION 2.

Venting and Combustion Air

WARNING

For indoor installations, as an additional measure

of safety, Laars strongly recommends installation of

suitable Carbon Monoxide detectors in the vicinity of

this appliance and in any adjacent occupied spaces.

AVERTISSEMENT

Pour des installations intérieures, Laars

recommande fortement, comme mesure de sécurité

supplémentaire, l’installation de détecteurs de

monoxyde de carbone adaptés dans le voisinage

de l’appareil et dans chacune des pièces habitées

adjacentes.

2.1 Combustion Air

Pennant boilers and water heaters must have

provisions for combustion and ventilation air in

accordance with the applicable sections addressing

requirements for air for combustion and ventilation of