To reset the switch, unscrew the black cover that

is over the reset button, and push the button. Replace

the cover after the switch is reset.

To replace, shut off power to the appliance.

Remove the cover that is over the button, and remove

the nut that is around the button. Pull the control

through the panel, and remove the spade terminals.

Replace in reverse order.

7.2.5 Temperature Control

The temperature control works with the ignition

control to ensure proper operation of the Pennant.

To replace the control, shut off the 120-volt power

to the appliance. Remove the cover from the control

panel, and remove the mounting screws to remove the

controller. Replace in reverse order.

7.2.6 Ignition Control

The ignition control controls the hot surface

ignitor and proves that the flame signal is appropriate

for powering the gas valves. It also controls the

blower’s pre-purge and post-purge.

To replace a control, shut off the 120-volt power

to the appliance. Remove the cover from the control

panel. Remove the electrical connectors from the

ignition control. Take out the controller’s mounting

screws, and pull the controller out. Replace in reverse

order.

7.2.7 Ignitor

The ignitor used is a 120v “Hot Surface” type.

It is energized whenever there is a call for heat and

switched off when ignition is established and the flame

has been sensed. To replace the ignitor, shut off the

120-volt power to the appliance, remove the ignitor/

burner access panel, disconnect the Molex connector,

remove the two mounting screws on the ignitor flange,

and pull the ignitor out. Install in reverse order, always

using a new ignitor gasket with the replacement

ignitor.

Caution

Ignitor gets hot. To avoid injury, handle the ignitor

with caution.

Attention

Le dispositif d’allumage devient très chaud.

Manipulez le dispositif d’allumage avec précaution.

7.2.8 Transformer

The Pennant’s transformer is not capable of

supplying control voltage for external devices such

as zone valves, which must have their own separate

power supply. Should a transformer need replacing,

shut off the 120-volt power. Unplug the transformer

wires, remove the mounting screws and remove the

transformer. Replace transformer in the reverse order.

7.2.9 Flow Switch

The Pennant uses a paddle-type flow switch to

ensure that the unit has water flow before ignition is

allowed. To replace the flow switch, turn off the 120-

volt power to the appliance. Isolate the boiler or water

heater from the system by closing the isolation valves.

Caution

Water may be hot enough to scald. Allow water to

cool before proceeding.

Attention

L’eau peut être chaude au point de vous brûler.

Laissez refroidir l’eau avant d’intervenir.

Release pressure in the system by actuating

the pressure relief valves or field supplied boiler

drain valve. Remove cover from the flow switch

and disconnect the wires. Unthread the flow switch

from piping. Ensure the new flow switch paddles are

trimmed to the same size as the original paddles, and

reinstall in the reverse order. For boiler and other static

pressure systems, restore the system pressure to the

original setting, (or 10 psi minimum).

7.2.10 Heat Exchanger Coil

WARNING

Black carbon soot buildup on a dirty heat exchanger

can be ignited by a random spark or flame thereby

creating a risk of fire or explosion. To prevent this

from happening, dampen the soot deposits with a

wet brush or fine water spray before servicing the

heat exchanger.

AVERTISSEMENT

L’accumulation de suie sur un échangeur thermique

sale peut s’enflammer au contact d’une étincelle ou

d’une flamme et présenter un risque d’incendie ou

d’explosion. Afin d’empêcher que cela se produise,

humidifier les dépôts de suie à l’aide d’une brosse

mouillée ou par une pulvérisation fine d’eau avant

d’effectuer l’entretien de l’échangeur thermique.

The Pennant has a premixed burner system.

These systems provide the burners with sufficient air

for complete combustion, and black carbon sooting is

seldom experienced. If sooting is suspected, view ports

for inspection of the heat exchanger are provided on

the side of the boiler. In the unlikely event that there is

a buildup of black carbon soot or other debris on the

heat exchanger, clean per the following:

1. Disconnect the electrical supply to the unit.

2. Turn off the gas supply by closing the manual gas

valve on the heater.