LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 36

Advertising
background image

LAARS Heating Systems

Page 34

Pennant 200, 300, 400

Page 35

3. Disconnect and remove the wires, conduit and

sensors from all components that are attached to

the inlet/outlet header.

4. Isolate the heat exchanger from the water supply.

5. Disconnect the header flanges from the inlet and

outlet.

6. Allow the heat exchanger to drain. Remove the

venting and remove the top, by removing the

screws that attach the top to the side panels.

Remove the side panels.

7. Remove the heat exchanger from the unit.

NOTE: Heat exchangers are heavy and may

require two people to remove to avoid personal

injury.

8. Clean the heat exchanger: A light accumulation

of soot or corrosion on the outside of the heat

exchanger can be easily removed. Use a wire

brush to remove loose soot and scale from the

heat exchanger.

9. NOTE: While the heat exchanger is out of the

unit, inspect the firewall refractory insulation.

Replace if necessary.

10. Inspect the inside of the copper tubes for scale

buildup. Scale can build up on the inner surface

of the heat exchanger tubes, which can restrict

water flow. If the tubes show signs of scaling,

clean the internal surface.

11. Reassemble in the reverse order, and check

appliance operation after start-up.

NOTE: The warranty does not cover damage

caused by lack of required maintenance, lack of

water flow, or improper operating practices.

SECTION 8.

Trouble Shooting

8.1 Resolving Lockouts

There are many causes of lockouts. The three

most common causes are: (1) inadequate gas supply,

(2) poor combustion, (3) ignitor failure.

1. Inadequate gas supply: Before proceeding, ensure

that the gas supply has not been shutoff or the LP

tank (LP boilers) is not empty. Then, restart the

boiler and observe the operational cycle. After

a 15-second fan pre-purge, the ignitor will heat

up for 40 seconds, and then the unit will light.

If it does not, check the gas supply pressure to

the appliance, after resetting the appliance and

attempting another start-up. The gas pressure to

the appliance must be above 5 in. w.c. (1.2 kPa)

throughout the entire start-up cycle. If it is not,

correct the supply problem (check gas valves or

supply piping). If the supply pressure is adequate,

consult the factory for assistance.

2. Poor Combustion: Poor combustion should be

suspected if there is a strong flue gas odor. The

odor may result from an improper gas/air ratio

(high or low O

2

or CO

2

). Pennant appliances

operate best with 45% excess air (8% CO

2

on

natural gas, 9.2% CO

2

on LP). Check the CO

2

of

the appliance and adjust if necessary.

3. Ignitor failure: If the boiler goes through a

normal start cycle but combustion does not

occur, ignitor failure should be suspected. Check

the ignitor by unplugging the ignitor plug and

measuring the ignitor resistance. It should be

50-80 ohms. If the resistance is not 50-80 ohms,

replace the ignitor. If the resistance is correct,

reset the boiler and check for 120 VAC at the

ignitor plug during the start cycle. If there is no

voltage, replace the faulty ignitor wire harness or

the ignition control.

8.2 Delayed Ignition — Possible Causes

A defective burner can cause a delayed ignition.

If the gas supply pressure is proper and the gas

valves are functioning properly, then burners should

be inspected. There should be no distortion or

perforations in the burners outside of the active burner

port area. Replace if indicated.

8.3 Short Cycling — Boiler

Boiler short cycling is caused when the load

on the boiler system swings rapidly causing frequent

cycling between call for heat and satisfied conditions.

This condition is greatly reduced on two stage units

or stage controlled multiple boiler systems which can

change heat input to better match the load. If short

cycling is a problem, it may be due to an oversized

boiler, improper control strategy, incorrect set points

or a load distribution problem. The boiler controls

must be set such that the heating loop temperature

setpoint, SP2 (if used), does not interfere with the

setpoint of the boiler operating control, SP1. If the

set points are correct and the system design, controls

scheme, etc. are fixed, the temperature differentials

may be increased to reduce short cycling. If desired

temperature response is not achievable without short

cycling it may be necessary to install a buffer tank

in the system. Contact your Laars representative to

discuss possible remedies.

8.4 Short Cycling — Water Heater

Short cycling will generally occur only in

combination space heating and water heating

applications when the water heater is operating in the

space-heating mode. If the heating load drops below

the minimum input of the water heater for an extended

period, the water heater will have a tendency to short

cycle. If short cycling is frequently experienced,

regardless of the control’s attempt to limit it, the

heating load should be redistributed to control it.

Advertising
This manual is related to the following products: