8.1.8 System Testing

The run screen is shown above. It shows the system is in manual mode with an average
height reading of 39 inches (100 cm).

CAUTION

In the following procedure, switch the control panel to manual mode
immediately if the boom movements are erratic.

Press the

button to start automatic mode. Observe the behavior of the booms while

correcting to the target height.

The run screen is shown above. It shows the system is in automatic mode with a target
height of 45 inches (114 cm).

The boom movements should be smooth and stable. Boom corrections should stop after a
few seconds under normal conditions (excessive wind may cause small corrections to
continue).

Press the

button to return to manual mode. If the boom corrections are done in an

acceptable manner, the system is ready to use.

** Automatic System Setup Complete **