Automatic Dead Zone Calibration:

•

Follow Section 8.1.1 (level booms, working RPM, etc.) before proceeding.

•

Ensure the UC4.5 control panel is in manual mode, at the run screen.

•

Navigate to the "More?" menu prompt in the SETUP (

) menu. Press

to confirm.

•

Navigate to the boom section to be set up, for example "Left?" to adjust the left up or the
left down settings. Press the

button to confirm.

•

Press the

button to access the next menu prompt. Choose the dead zone up or down

setting (Figure 10).

•

Press and hold the

button.

•

When the "Done" message is displayed, release the

button to view the new setting.

Manual Dead Zone Calibration:

•

Follow Section 8.1.1 (level booms, working RPM, etc.) before proceeding.

•

Ensure the UC4.5 control panel is in manual mode, at the run screen.

•

Navigate to the "More?" menu prompt in the SETUP (

) menu. Press

to confirm.

•

Navigate to the boom section to be setup, for example, "Left?" to adjust the left up and/or
the left down settings. Press the

button to confirm.

•

Press the

button to access the next menu prompt. Choose the dead zone up or down

setting (Figure 10).

•

Press and hold the

button.

•

The valve will turn on at the indicated setting for exactly one second. The screen will show
the actual change in height.

•

The change in height reading is live as long as the

button is held. Wait until the height

reading has settled to a stable value and record this reading.

•

Average three readings. The acceptable average change in height should be from 0.5 to 1.5
inches (13 to 38 mm). Ideal would be 1 inch exactly (25 mm).

•

If the average is less, increase the DZ setting with the

button. If the average is more,

decrease the DZ setting with the

button.

•

Repeat the manual dead zone test until the average falls into the acceptable range.