Id plug 4, Code 2 and 14 - plug-in relay, omron – Reznor SDH Parts Manuals User Manual

Page 4

Advertising
background image

Form P-PREEVA, P/N 263985R7, Page 4

Electrical Components (cont’d) - See control compartment illustration on page 3.

CODE 1A - Phase Loss

Control (Option BF15),

Auto Reset,

3Ph,

P/N 206105

CODE 1B - Phase Loss/Over

and Under Voltage Control

(Option BF14),

Auto Reset, 3Ph,

P/N 176826

Socket, P/N 194168

(not illustrated)

CODE 2 and 14 - Plug-in Relay, Omron

Relay 3PDT, 24VAC, P/N 211799

Socket for 3PDT relay, P/N 211800

Relay, DPDT, LY2-AC24, P/N 211411

Relay, DPDT, LY2-AC110/120, P/N 211412

Relay, DPDT, LY2-AC200/220, P/N 211413

Relay, DPDT, LY2-AC220/240, P/N 211414

Socket for DPDT relays, P/N 211415

CODE 7A - Variable

Frequency Drive

Control (Opt VFD)

and Matching Line

Reactor

CODES 18A

and 18B -

Combustion

Air Pressure

Switches for

Gas-Fired

Models

CODE 6 - Fuse, #Mdq

1-1/2, for DG Options,

P/N 193803

Fuseholder, P/N 60241

CODE 5 - Terminal

Board for Thermostat

with AG Options only,

P/N 164545

Transformers,

CODES 3, 4,

10, and 13

CODE 15 - DSI Integrated

Control Module for PDH/

SDH/SHH/RDH/RHH with

all gas controls except

AG58 or D12G, P/N 195573

(Serial No. Code 78)

PDH/

SDH/

RDH

High Speed for sea level to

6000 ft (1830M) elevation

High Speed for above

6000 ft (1830M) elevation

Low Speed for all elevations

(applies to units with 2-speed

venter only)*

Switch P/N Setting (" w.c.) Switch P/N Setting (" w.c.) Switch P/N Setting (" w.c.)

75

197030

0.4

197031

0.35

205442

0.2

100

197030

0.4

197031

0.35

205444

0.3

125

196388

0.5

197032

0.45

205444

0.3

150

197028

0.65

197029

0.6

205444

0.3

175

201158

1.1

201160

1.05

197030

0.4

200

201158

1.1

201160

1.05

197030

0.4

225

201158

1.1

201160

1.05

197030

0.4

250

201158

1.1

201160

1.05

197030

0.4

300

201158

1.1

201160

1.05

197030

0.4

350

201158

1.1

201160

1.05

197030

0.4

400A

201158

1.1

201160

1.05

197030

0.4

Mtr HP

& Type

VFD Drive and

Matching Line

Reactor

208/1/60

230/1/60

208/3/60 230/3/60

480/3/60

575/3/60

ODP TEFC ODP TEFC Prem ODP TEFC Prem ODP TEFC Prem

1/2 Drive

221600

221605

N/A

221612

N/A

N/A

Line Reactor

221595

221598

221590

3/4 Drive

N/A

221606

N/A

221613

N/A

N/A

Line Reactor

221598

221591

1

Drive

221601

221607

221614

N/A

Line Reactor

221596

221594

221592

1-1/2 Drive

221602

221608

221615

N/A

Line Reactor

221597

221595

221593

2

Drive

221603

221609

221616

221855

Line Reactor

221597

221596

221585

NA (Built-in)

3

Drive

221604

221610

221617

221856

Line Reactor

221599

221597

221586

NA (Built-in)

5

Drive

N/A

221611

221618

221857

Line Reactor

221599

221587

NA (Built-in)

NOTE: Blower off delay DIP

switches to be adjusted to

45 seconds for makeup air

applications. Refer to the table

on the control for the settings.

Volts In

Volts Out VA

P/N

115

24

40

194808

208/230

24

40

194536

120/208/240/480

24

75

208989

460/575

230

200

210862

460/575

230

350

210863

CODE 9 - Air

Proving Switch,

0.10” w.c.,

P/N 234712

CODE 8 - Dirty Filter

Switch, P/N 105507

Code 15B - ID Plugs for Models RHH & SHH with

Serial No. Ignition Code 99 (P/N 260917)

ID Plug

P/N

ID Plug

Label

Heat Size

Gas

258101 SHH 130NG

130

Natural

258102 SHH 130LP

Propane

258103 SHH 180NG

180

Natural

258104 SHH 180LP

Propane

258105 SHH 260NG

260

Natural

258106 SHH 260LP

Propane

258107 SHH 350NG

350

Natural

258108 SHH 350LP

Propane

CODE 15 - DSI Integrated Control Module for SHH & RHH w/gas control Opt

AG58 or D12G, Varidigm VB1200-5-RZNR-SHH, P/N 260917 (Serial No. Code 99)

CODE 15B -

ID Plug only

CODE

15A -

Fuse

Only,

P/N

201685

CODE 15 - DSI Integrated Control Module for RDH with

gas control Opt AG58 or D12G, Varidigm VB1200-2-

RZNR-PVA, P/N 260252 (Serial No. Code 98)

Code 15B - ID Plugs for Model RDH w/Ignition CODE 98 (P/N 260252)

ID Plug P/N

ID Plug Label

Heat Section

Gas

258081

PREEVA 175NG

175

Natural

258082

PREEVA 175LP

Propane

258083

PREEVA 200NG

200

Natural

258084

PREEVA 200LP

Propane

258085

PREEVA 225NG

225

Natural

258086

PREEVA 225LP

Propane

258087

PREEVA 250NG

250

Natural

258088

PREEVA 250LP

Propane

258089

PREEVA 300NG

300

Natural

258090

PREEVA 300LP

Propane

258091

PREEVA 350NG

350

Natural

258092

PREEVA 350LP

Propane

258093

PREEVA 400NG

400

Natural

258094

PREEVA 400LP

Propane

Replacement Display,

ABB Model ACS-CP-A,

P/N 272508

* Gas Control Options AG40, AG60, AG61, AG62, DG1, DG2, DG5, DG6, D12B & D12C.

High Speed

SHH/

RHH

with Options

AG2 or D12F

with Option

AG58 or D12G

Switch

P/N

Setting

(" w.c.)

Switch

P/N

Setting

(" w.c.)

130

201161

1.30

201160

1.05

180

201161

1.30

201160

1.05

260

201159

1.40

201160

1.05

350

221228

2.30

201160

1.05

RDH

with Option AG58 or D12G

Switch P/N

Setting (“w.c.)

175

197029

0.60

200

197078

0.80

225
250

205446

0.70

300
350

400A

Advertising