Electrical components - replacement p/n’s (cont’d) – Reznor P125 YDSA Parts Manuals User Manual
Page 18

Form P-Y (01-15), PN 273651R6, Page 18
* Heat sections with dual furnaces. When only one size is listed, both furnaces are the same size and two identical high pres-
sure switches are used. Dual furnace heat sections with electronic modulation Option AG74 have one low pressure switch.
Code No’s 32 & 33 Combustion Air Switches for Sea Level to 6000 ft. (1830 m)
Heat
Section
Option
Heat
Size(s)
(Btuh)
Code #32 High Pressure Switch
Code #33 Low Pressure Switch (AG73 & AG74 Only)
Startup
Cold
Equilibrium
Hot
Setpoint
Off
Label
Color
Switch
P/N
Startup
Cold
Equilibrium
Hot
Setpoint
Off
Label
Color
Switch
P/N
230, 460,
575V
% Full
Speed of
Venter Mtr
208V
% Full
Speed of
Venter Mtr
Negative Pressure (iwc)
Negative Pressure (iwc)
H50
50,000 3.10
2.00
1.50 Yellow 273360
3.50
1.30
0.75
Yellow 205443
74
82
H75
75,000 3.30
1.60
1.40
Red
201159
3.30
1.30
1.00
Brown 201160
74
82
H100 100,000 3.40
1.70
1.40
Red
201159
3.40
1.20
1.00
Brown 201160
74
82
H102* 50,000 3.10
2.00
1.50 Yellow 273360
3.50
1.30
0.75
Yellow 205443
74
82
H125* 50,000
3.10
2.00
1.50 Yellow 273360
(No low pressure switch on this furnace)
75,000 3.30
1.60
1.40
Red
201159
3.30
1.30
1.00
Brown 201160
74
82
H150* 75,000 3.30
1.60
1.40
Red
201159
3.30
1.30
1.00
Brown 201160
74
82
H175* 75,000
3.30
1.60
1.40
Red
201159
(No low pressure switch on this furnace)
100,000 3.40
1.70
1.40
Red
201159
3.40
1.20
1.00
Brown 201160
74
82
H200 200,000 3.80
1.80
1.40
Red
201159
3.80
0.90
0.75
Yellow 205443
42
54
H202* 100,000 3.40
1.70
1.40
Red
201159
3.40
1.20
1.00
Brown 201160
74
82
H300 300,000 3.90
1.90
1.50 Yellow 273360
3.90
0.90
0.75
Yellow 205443
48
56
H400 400,000 3.80
1.80
1.50 Yellow 273360
3.80
1.00
0.80
Gray 197078
58
64
H402* 200,000 3.80
1.80
1.40
Red
201159
3.80
0.90
0.75
Yellow 205443
42
54
H502 200,000
3.80
1.80
1.40
Red
201159
(No low pressure switch on this furnace)
300,000 3.90
1.90
1.50 Yellow 273360
3.90
0.90
0.75
Yellow 205443
48
56
H602* 300,000 3.90
1.90
1.50 Yellow 273360
3.90
0.90
0.75
Yellow 205443
42
56
H702 300,000
3.90
1.90
1.50 Yellow 273360
(No low pressure switch on this furnace)
400,000 3.80
1.80
1.50 Yellow 273360
3.80
1.00
0.80
Gray 197078
58
64
H802* 400,000 3.80
1.80
1.50 Yellow 273360
3.80
1.00
0.80
Gray 197078
58
64
Heat
Section
Option
Heat
Size(s)
(Btuh)
Code #32 High Pressure Switch
Code #33 Low Pressure Switch (AG73 & AG74 Only)
Startup
Cold
Equilibrium
Hot
Setpoint
Off
Label
Color
Switch
P/N
Startup
Cold
Equilibrium
Hot
Setpoint
Off
Label
Color
Switch
P/N
230, 460,
575V
% Full
Speed of
Venter Mtr
208V
% Full
Speed of
Venter Mtr
Negative Pressure (iwc)
Negative Pressure (iwc)
G150 150,000 2.70
2.20
1.40
Red
201159
2.70
1.70
0.10
White 234712
61
74
G225 225,000 2.90
2.50
1.40
Red
201159
2.90
1.30
0.10
White 234712
61
74
G300 300,000 2.70
2.50
1.30
White 201161
2.70
0.90
0.10
White 234712
61
74
G302* 150,000 2.70
2.20
1.40
Red
201159
2.70
1.70
0.10
White 234712
61
74
G372 150,000
2.70
2.20
1.40
Red
201159
(No low pressure switch on this furnace)
225,000 2.90
2.50
1.40
Red
201159
2.90
1.30
0.10
White 234712
61
74
G452* 225,000 2.90
2.50
1.40
Red
201159
2.90
1.30
0.10
White 234712
61
74
G525 225,000
2.90
2.20
1.40
Red
201159
(No low pressure switch on this furnace)
300,000 2.70
2.50
1.30
White 201161
2.70
0.90
0.10
White 234712
61
74
G602* 300,000 2.70
2.50
1.30
White 201161
2.70
0.90
0.10
White 234712
61
74
Electrical Components - Replacement P/N’s (Cont’d)
For Component Location: Cabinet 1A & 1B, see pages 5, 6 & 10; Cabinet 2, see pages 7 & 10, Cabinet 3, see
pages 8, 9 & 10. For an Illustration of most parts, see pages 12, 16 & 17.