Form P-Y (01-15), PN 273651R6, Page 2

System Rating Plate Key:

A = Model

B = Manufacturing Date

(Month/Year)

C = Blower Motor HP

D = Volts/Phase/Hertz

E = Full Load Amps (FLA) of

Blower Motor

F = Minimum Circuit

Ampacity (MCA)

G = Maximum Fuse Size

(MOP)

H = Quantity - Compressor A

I = Rated Load Amps of

Compressor A

J = Locked Rotor Amps of

Compressor A

K = Quantity - Compressor B

L = Rated Load Amps of

Compressor B

M = Locked Rotor Amps of

Compressor B

N = Quantity - Compressor C

O = Rated Load Amps of

Compressor C

P = Locked Rotor Amps of

Compressor C

Q = Quantity - Compressor D

R = Rated Load Amps of

Compressor D

S = Locked Rotor Amps of

Compressor D

V = Refrigerant Charge (lbs) -

Circuit A

W = Refrigerant Charge (lbs)

- Circuit B

X = Refrigerant Charge (lbs) -

Circuit C

Y = Refrigerant Charge (lbs) -

Circuit D

Z = Condenser Fan Motor HP

CC = SCFM Airflow

DD = External Static

Pressure (“ w.c.)

FF = Wiring Diagram No.

GG = Quantity - Compressor

Low Enthalpy

HH = Rated Load Amps

of Compressor Low

Enthalpy

JJ = Locked Rotor Amps

Compressor Low

Enthalpy

KK= Quantity - Compressor

High Enthalpy

LL= Rated Load Amps

of Compressor High

Enthalpy

MM= Locked Rotor Amps

Compressor High

Enthalpy

NN= Refrigerant Charge (lbs)

- RPLE Circuit

PP= Refrigerant Charge (lbs)

- RPHE Circuit

Rating Plates and Serial No.

Decoding a System Serial No.
Serial No. Sample: 3 BIJ 789 BK 08 N 96 7D

Elements of No.: 1| 2 | 3 | 4 | 5 |6| 7 | 8

Elements 1-5 apply to all models.

Elements 6-8 apply to models with gas heat section (YDHA, YDMA & YDSA).
Key:
1 = Phase (1 or 3)

2 = Date CODE (See table top of page 3.)

3 = Consecutive number

4 = Not Applicable

5 = Motor HP (See explanation on the right.)

6 = Type of Gas - Models YDHA, YDMA & YDSA (N = Natural; L = Propane)

7 = Ignition CODE - Models YDHA, YDMA & YDSA (See Form P-Valve)

8 = Valve CODE - Models YDHA, YDMA & YDSA (See Form P-Valve)

Supply Air Blower Motor

Motor HP

Serial No.

Code

3 (3450 rpm)

08

5 (3450 rpm)

09

10

13

20

14

Sample of System Rating Plate (applies to all Y series models)

DANGER

This unit contains R-410A high pressure refrigerant. Hazards exist that could result

in personal injury or death. Installation, maintenance, and service should only be

performed by an HVAC technician qualified in R-410A refrigerant and using proper

tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT

USE service equipment or tools designed for R22 refrigerant.

MERCER, PA., U.S.A. 16137

MADE IN USA

FOR INDUSTRIAL/COMMERCIAL USE ONLY

SUITABLE FOR OUTDOOR USE

MODEL [ A ]

[ B ]

SERIAL NO. [ ]

[D] VOLTS +/- 10% [D] PHASE [D] HZ
MINIMUM CIRCUIT AMPACITY (MCA)

[ F ] AMPS

MAXIMUM FUSE SIZE/*CKT BREAKER

[ G ] AMPS

SHORT-CIRCUIT CURRENT: 5,000 A RMS SYMMETRICAL

[D] V MAX.

MAXIMUM OUTLET TEMPERATURE [ X ]

QTY

FLA (EA) HP (EA)

SUPPLY AIR BLOWER MOTOR

1

[ E ]

[ C ]

CONDENSER FAN MOTOR (S)

[ T ]

[ U ]

[ Z ]

QTY

RLA (EA) LRA (EA)

COMPRESSOR A

[ H ]

[ I ]

[ J ]

COMPRESSOR B

[ K ]

[ L ]

[ M ]

COMPRESSOR C

[ N ]

[ O ]

[ P ]

COMPRESSOR D

[ Q ]

[ R ]

[ S ]

COMPRESSOR LOW ENTHALPY

[ GG ]

[ HH ]

[ JJ ]

COMPRESSOR HIGH ENTHALPY

[ KK ]

[ LL ]

[ MM ]

CIRCUITS

A

B

C

D

LE

HE

REFRIGERANT - R-410a CHARGE - LBS

[ V ] [ W ] [ X ] [ Y ] [NN] [PP]

TEST PRESSURES

HIGH

600 PSIG LOW

45 PSIG

EQUIPPED FOR OPERATION AT AN AIR FLOW OF

[ CC ] SCFM

AGAINST A STATIC PRESSURE OF

[ DD ] INCHES WATER COLUMN

WIRE DIAGRAM

[ FF ]

*HACR TYPE REQUIRED PER NEC
CLEARANCES TO COMBUSTIBLE CONSTRUCTION AND FOR SERVICE:
TOP - 60”, CONDENSER SIDE - 48”
CONTROL SIDE WITH GAS HEAT - 84”
CONTROL SIDE WITH ELECT OR NO HEAT - 36”
BOTTOM - 0”, INLET AIR SIDE - 24”, COIL/FILTER ACCESS SIDE - 72”

Serial No. Decoding