Two Pipe

Lift Ht.

1/2" O.D. Tubing

A

B

5/8" O.D. Tubing

A

B

A = B82 Series Suntec Pump 63 GPH gear capacity.

B = B89 Series Suntec Pump 75 GPH gear capacity.

Table 8. Line Length for Two-Stage Fuel Unit

Components usually required are a motorized booster pump of sufficient capaci-
ty, gravity tank and mounting hardware, automatic oil level pressure switch, vac-
uum breaker and necessary check valves and fittings. Additional information can
be obtained from Mitco Manufacturing, Hicksville, New York.

Duplex booster pumps are desirable to provide standby capability, in the event of
booster pump failure.

Sizing booster pump
To determine the correct size of a booster pump:

a) Using Table 1, find maximum total firing rate of the boiler system being

installed.

b) Find the vertical and horizontal dimensions of the booster pump's suction line.
c) Make sure the suction line lift and length are with capabilities of typical boost-

er pumps. Refer to Table 5. (This data is based on Suntec models BH-1030M
at 30 GPH, and BH-1050M at 50 GPH or equivalent.)

NOTE: If lift is excessive (max. 6" Hg one stage, 15" Hg two stage), contact
pump manufacturer with exact requirements. If total length is too long, increase
suction line diameter.

d) Using Table 6, find correct supply line size.

Figure 17.

Wiring diagram for

gravity feed

booster- pump operation

0 - 7'

100'

63'

8 - 10'

80'

53'

11 - 13'

63'

41'

14 - 15'

52'

34'

Vertical

Lift (2)

Firing Rates

up to 30 GPH (5)

Firing Rates

up to 50 GPH (6)

Maximum Total Suction Line Lengths (3)

1/2" O.D. copper tubing (4)

Table 5. Maximum booster pump suction line length (1)

25'

1

2

" O.D. tube

1

2

" O.D. tube

75'

1

2

" pipe

1

2

" pipe

200'

3

4

" pipe

3

4

" pipe

Total Length

Maximum

Firing Rates

up to 30 GPH (5)

Firing Rates

up to 50 GPH (6)

Table 7. Boiler feed line sizes (9)

Up to 30 GPH (5)

300'

800'

2500'

Up to 50 GPH (6)

175'

350'

1500'

Supply Line Size

1

2

" O.D. tube

1

2

" pipe

3

4

" pipe

Firing Rate

Maximum Total Supply Line Length (8)

Table 6. Supply line sizes for high-volume fuel oil

delivery systems (7)

(1) Defined as the connection distance between storage tank and inlet of booster pump.

(2) Height of booster pump inlet above bottom of storage tank. If higher lift is

needed, contact booster pump manufacturer with exact requirements.

(3) Total suction length equals vertical lift plus horizontal distance between suction

line connection at storage tank and inlet of booster pump.

(4) 5/8" tubing allows maximum horizontal distance between supply tank outlet

and booster pump inlet to be safely increased by 250%.

(5) Maximum fuel oil consumption rate with Suntec BH-1030M pump.

(6) Maximum fuel oil consumption rate with Suntec BH-1050M pump.

(7) Supply line is defined as the connection between the outlet of the booster

pump and the inlet of the supply tank.

(8) Total supply line length equals vertical lift plus horizontal distance between

booster pump outlet and supply tank inlet.

(9) Boiler feed line is defined as the connection between the gravity feed tank and

the furthest burner.