8

BOILER ROOM DESIGN

Caravan modular boiler systems allow better utilization of floor
space and permit future expansion with minimum cost. Caravan
modules are hand truckable, fit through doorways and often may
be installed around an existing inoperative boiler. They can be
grouped in heating module batteries of single, multiple or angular
rows. Oil-fired boiler systems consisting of 9 or more modules
should be piped in parallel in two or more batteries. Illustrated
below are typical boiler room layouts and dimensional data on the
size requirements of oil-fired hot water boilers.

BOILER ROOM AIR SUPPLY

To ensure safe, efficient operation, the modular boiler system must
be supplied with sufficient air to support complete combustion,
replacing air entering draft dampers or draft hoods and ventilating
the boiler room or areas. For additional information, not listed
below, see ANSI,Z223.1, section 5.3.3.

INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF
AIR INTO THE BOILER ROOM:

1. Air drawn horizontally from outdoors DIRECTLY

through an outside wall; one louvered opening near
the floor (below burner air inlet) and one louvered
opening near the ceiling (above the highest draft
regulator), each opening with a minimum FREE air
passage area of 1 square inch per 4000 BTUH of total
system input.

2. Air drawn horizontally from outdoors through

HORIZONTAL DUCTS; one opening near the floor (below
burner inlet) and one opening near the ceiling (above the
highest draft regulator), each opening with a minimum
FREE air passage area of 1 square inch per 2000 BTUH
of total system input.

3. Air drawn VERTICALLY from outdoors; one opening

at the floor and one opening at the ceiling, each opening
with a minimum FREE air passage area of 1 square inch
per
4000 BTUH of total system input.

4. Air drawn from inside the building; one opening near

the floor (below burner inlet) and one opening near the
ceiling (above the highest draft regulator), each opening
with a minimum FREE air passage area of 1 square inch
per 1000 BTUH
of total system input.

IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL

BURNING EQUIPMENT, THE AREA OF FREE OPENINGS

MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE

THE ADDITIONAL LOAD.

UNLESS PROPERLY CONTROLLED, AVOID THE USE OF

FORCED VENTILATION, SINCE IT CAN CREATE AN

UNDESIRABLE PRESSURE DIFFERENTIAL BETWEEN

BOILER ROOM AND AIR SOURCE.