EC-25

P2-KA

Short

1.55

1.25

60˚ B

Delavan

155

8

4.5

EC-26

P2-KA

Short

1.9

1.5

60˚ B

Hago

160

9

8

EC-27

P2-KA

Short

2.25

1.75

60˚ B

Hago

165

15

11

EC-28

P2-K

Short

2.5

2

60˚ B

Delavan

155

8

10

Boiler

Model

Burner

Model

Blast

Tube

Firing

Rate

GPH

Size

(GPH)

Angle &

Type

Mfg.

Oil Pump

(PSIG)

Approx.

Head

Setting

Approx.

Air

Setting

Nozzles

FIRING HEAD ADJUSTMENT

By turning the head adjustment screw clockwise, the
burner head will move inside the blast tube

AWAY

from

the end cone. This achieves lower firing rates. Similarly,
by turning the head adjustment screw

counter-clock-

wise,

the burner head will move inside the blast tube

toward the end cone, increasing the firing rate.

AIR SHUTTER ADJUSTMENT

Air adjustment is set at the factory. By turning the air
adjustment screw clockwise, the air shutter opening
increases. To achieve proper combustion, the air shutter
may need to be adjusted.

Head adjustment

Air band

adjustment

Scale

Scale

Picture 10

Figure 9

Figure 11

Figure 12

HEAT WISE BURNER DATA – BURNERS MODEL P2-KA and P2-K