EUTECTIC EC-20

2

Maximum operating pressure 60 psi.
All boilers hydrostatically tested — A.S.M.E.
* For forced hot water heating systems where the boiler and all piping are

located within the area to be heated, the boiler may be selected on the basis
of D.O.E. capacity output. The net AHRI output ratings shown are based on
an allowance for piping and pickup of 1.15 (water). D.O.E. capacity output is
divided by the allowance to obtain net rating. The Slant/Fin Technical Service
department should be consulted before selecting a boiler for unusual piping
and pickup requirements such as intermittent system operation, extensive
piping, etc.

† Ratings apply to the use of light oil at 140,000 Btu per gallon and apply only

when burner models listed on page 12 of this manual are used, and are
properly adjusted to produce 13% CO2.

# All dimensions subject to normal manufacturing tolerance.
NOTE: All boilers under 300,000 Btuh (87.9 kw) input are tested and rated for
capacity under the U.S. Department of Energy (D.O.E.) Test Procedures for
Boilers.

TABLE 1: Ratings and Dimensions

EC-25

1.55 217,000

190

165

6 x 15 86.5

N/A

32-9/16

35-3/8

46-3/8

6

20

2

EC-26

1.90 266,000

232

202

7 x 15 86.5

N/A

37-9/16

40-3/8

51-3/8

7

25

2

EC-27

2.25 315,000

269

234

7 x 15

N/A

85.3

42-9/16

45-3/8

56-3/8

7

30

2

EC-28

2.50 350,000

298

259

7 x 15

N/A

85.3

47-9/16

50-3/8

61-3/8

7

35

2

BOILER

MODEL

NO.

GPH

BTUH

AHRI

BURNER

CAPACITY

OIL INPUT † §

D.O.E.

HEATING

CAPACITY

MBH *

WATER

APPROX.

OVERALL

LENGTH

“A”

THERMAL

EFF. (%)

AHRI

WATER

NET

RATING

MBH *

AHRI

CHIMNEY SIZE

DIMENSIONS (inches) #

I.D. ROUND

X HEIGHT

(in x ft)

AFUE

%

BOILER

LENGTH

“B”

BOILER

LENGTH

“C”

FLUE

DIA.

“D”

DISTANCE
BETWEEN

LEGS

“E”

FLUE

OUTLET

LENGTH

“F”

Figure 1: Dimensions

Air Eliminator
as per Manufacturer
Specifications

To Circ. (s)
and Zones

1-1/2”

NPT

Supply

Automatic
Air Vent

Suppy Pipe Mounted

Tridicator

A

1-1/2”

NPT

Return

3/4”
NPT

Drain

D

Advertising