11.6 - Convert the
boiler from Natural
Gas to Propane gas
or viceversa

WARNING!!!

The gas

conversion shall be performed
by a qualifi ed service agency
in accordance with this
instructions and all applicable
codes and requirements of the
authority having jurisdiction.
The information in these
instructions must be followed
to minimize the risk of fi re
or explosion or to prevent
property damage, personal
injury or death. The qualifi ed
service agency is responsible
for the proper conversion of
the boiler. The installation is
not proper and complete until
the operation of the converted
appliance is checked as
specifi ed in this instructions.

WARNING!!!

The

conversion shall be carried
out in accordance with
the requirements of the
provincial authorities having
jurisdition and in accordance
with the requirements of the
CAN-B149.1
and CAN1-B149.2
installation code.

Contents:
The conversion kit (supplied with the
boiler) is composed of the following
elements, which are necessary for the
gas change:
- a label rating the new gas setting;

- an instruction sheet;
- an orifi ce;

Installing:
in order to make the gas change
please follow the instructions below:

1 - turn off power to the boiler;

2 - open the boiler’s casing (Follow

Section 14.2);

3 - open the instrument panel (Follow

Section 9.2);

4 - Move switch #7 (see Figure 9-2)

from OFF position to ON position;

5 - turn on power to the boiler;

6 - on the boiler’s display you’ll see

followed by a number;

7 - using the push buttons

and

set the input

to:

- 61 to convert the boiler from LP

GAS to NATURAL GAS

or

- 62 to convert the boiler from

NATURAL GAS to LP GAS,

8 - push

button to save the

new value;

9 - turn off power to the boiler;

10 - Move switch #7 (see Figure 9-2)

from ON position to OFF position;

11 - Replace the orifi ce item “C” of

Figure 11-2 for the correct one for
the type of gas used. Verify that the

Gas Type

TY value

setting

Min.

supply

pressure

Max.

supply

pressure

Orifi ce

CO2

content at

high fi re

CO2

content at

low fi re

O2

content at

high fi re

O2 content

at low fi re

CO content at

high and low fi re

/

/

in.W.C.

in.W.C.

Stamping

%

%

%

%

ppm

Natural gas

61

3

13

9.1

9.2 ± 0.1

8.7 ± 0.3

4.5 ± 0.1

5.4 ± 0.3

less than 150

LP gas

62

3

13

5.7

9.5 ± 0.2

9.5 ± 0.3

6.4 ± 0.2

6.4 ± 0.3

less than 250

Table 11-3 Settings of the boiler for NATURAL GAS and LP GAS

11 - INSTALLATION - Gas supply

stamping on the orifi ce matches the
gas type (See Table 11-3).

11 - turn on power to the boiler;

12 - Turn completely counter

clockwise the screw E of Figure
11-2;

13 -

Checking gas supply pressure

following Section 12.7.

The Gas

supply pressure must be between
the maximum and minimum value
as stated in Table 11-3.

14 - Verifying the CO2 rate and its

eventual adjustment following
Section 12-9: The boiler during
its normal operation, within a
maximum altitude of 2000 ft, has
a CO2 exhaust rate as shown in
Table 11-3. If not within range of
value shown, malfunctions will
occur.

WARNING!!!

The CO

(carbon monoxide) level should
not exceed values given in
Table 11-3, when combustion is
correct. Failure to comply with
this requirement could result in
severe personal injury, death or
substantial property damage.

WARNING!!!

All

combustion measurements
must be performed with
calibrated equipment to ensure
proper reading and accuracy.
Failure to comply with this
requirement could result in
severe personal injury, death or
substantial property damage.