A = Fixing nut
B = Gasket
C = Orifi ce
D = Brass fi tting
E = CO2 / O2 regulator
WARNING!!!
If the
combustion levels are not
within the range given in Table
11-3 for the fi ring rate, shut
the boiler down and contact
your distributor or the boiler
manufacturer (see reference in
the last cover page). Failure to
comply with this requirement
could result in severe personal
injury, death or substantial
property damage.
15 - Attach to the front of the boiler
the appropriate conversion label,
found in the conversion kit (see
Figure 11-3 or Figure 11-4), stating
the new type of gas adjustment of
the boiler.
a - Apply the label in Figure 11-4 if
the boiler has been converted to
LP GAS;
b - Apply the label in Figure 11-3 if
the boiler has been converted to
NATURAL GAS.
11 - INSTALLATION - Gas supply
Figure 11-3 Label for Natural gas boiler
Figure 11-4 Label for LP gas boiler
Figure 11-2 Gas valve