EH-M3-40 Boiler Operation and Installation Instructions

Table 1. Lug Sizes

Table 2. Flow Switch Size Selection

* Straight pipe upstream and downstream of flow switch.

Model No.

Flow Switch

McDonnell & Miller No.

Pipe

Size

Minimum

Pipe Length*

EH-8-M3 thru EH-20-M3

FS4-3T3-1

1"

6-1/2”

Distribution Block

Grounding Lug

Neutral Lug

Wire Size

Wire Size

Wire Size

Model

Phase

CU-AL†

CU-AL†

CU-AL†

EH-8 thru 20

1

6-2/0

6-2/0

6-2/0

EH-12 thru 20

3

6-2/0

6-2/0

6-2/0

Neutral Lug Wire Size:For 3-wire single phase and 4-wire 3 phase
models equipped with circuit breakers. The neutral tap is for the
circulator and control transformer.

ALUMINUM conductors may be used, lug size, conduit size, ampacity and all
applicable codes permitting.

Table 3. Current Ratings

† Leg with the highest value of line current of an unbalanced 3-phase load.
‡ 125 VAC maximum rating of all hot conductors.

SINGLE PHASE 3 WIRE, 120/208V‡

Basic Model

No.

Heater Amperes

@ 208V

EH8-13-8-M3

EH10-13-8-M3
EH12-13-8-M3
EH16-13-8-M3
EH20-13-8-M3

29
36

43.4

58
72

SINGLE PHASE 3 WIRE, 120/240V‡

Basic Model

No.

Heater Amperes

@ 240V

EH8-13-4-M3

EH10-13-4-M3
EH12-13-4-M3
EH16-13-4-M3
EH20-13-4-M3

33
42
50
67
83

THREE PHASE 4 WIRE, 120/208V

WYE CIRCUIT ONLY‡

Basic Model

No.

Heater Amperes †

@ 208V


EH12-34-8-M3
EH16-34-8-M3
EH20-34-8-M3


43

58

72

THREE PHASE 4 WIRE, 120/240V

DELTA CIRCUIT ONLY‡

Basic Model

No.

Heater Amperes †

@ 240V


EH12-34-4-M3
EH16-34-4-M3
EH20-34-4-M3


50

67

83