Slant/Fin EH-M3 User Manual

Page 4

Advertising
background image

4

EH-M3-40 Boiler Operation and Installation Instructions

Table 1. Lug Sizes

Table 2. Flow Switch Size Selection

* Straight pipe upstream and downstream of flow switch.

Model No.

Flow Switch

McDonnell & Miller No.

Pipe

Size

Minimum

Pipe Length*

EH-8-M3 thru EH-20-M3

FS4-3T3-1

1"

6-1/2”

Distribution Block

Grounding Lug

Neutral Lug

Wire Size

Wire Size

Wire Size

Model

Phase

CU-AL†

CU-AL†

CU-AL†

EH-8 thru 20

1

6-2/0

6-2/0

6-2/0

EH-12 thru 20

3

6-2/0

6-2/0

6-2/0

Neutral Lug Wire Size:For 3-wire single phase and 4-wire 3 phase
models equipped with circuit breakers. The neutral tap is for the
circulator and control transformer.

†

ALUMINUM conductors may be used, lug size, conduit size, ampacity and all
applicable codes permitting.

Table 3. Current Ratings

† Leg with the highest value of line current of an unbalanced 3-phase load.
‡ 125 VAC maximum rating of all hot conductors.

SINGLE PHASE 3 WIRE, 120/208V‡

Basic Model

No.

Heater Amperes

@ 208V

EH8-13-8-M3

EH10-13-8-M3
EH12-13-8-M3
EH16-13-8-M3
EH20-13-8-M3

29
36

43.4

58
72

SINGLE PHASE 3 WIRE, 120/240V‡

Basic Model

No.

Heater Amperes

@ 240V

EH8-13-4-M3

EH10-13-4-M3
EH12-13-4-M3
EH16-13-4-M3
EH20-13-4-M3

33
42
50
67
83

THREE PHASE 4 WIRE, 120/208V

WYE CIRCUIT ONLY‡

Basic Model

No.

Heater Amperes †

@ 208V

–
–

EH12-34-8-M3
EH16-34-8-M3
EH20-34-8-M3

–
–

43

58

†

72

†

THREE PHASE 4 WIRE, 120/240V

DELTA CIRCUIT ONLY‡

Basic Model

No.

Heater Amperes †

@ 240V

–
–

EH12-34-4-M3
EH16-34-4-M3
EH20-34-4-M3

–
–

50

67

†

83

†