EH-M3-40 Boiler Operation and Installation Instructions

Field Entry

Low Temperature System

Note

MODE

4 or 5

4 = Parallel Piping, 5 = Primary/Secondary Piping

STGMODE

PID

P

P

BOIL TARGET

180

180

180

This is for DHW setpoint demand - if used

OUTDR START

70

70

70

OUTDR DSGN

-10

-10

-10

May be -20 or -30F depending on area design temp.

BOIL START

70

70

70

This is used in the calculation of slope

BOIL DSGN

180

180

130

Radiant - 130 Wet, 140 or 150F for Dry system

BOIL OUT MAX

200

200

150

Default 200 - Use "FACTORY" Dip Switch to Adjust
Can be set 10F over BOIL DSGN

BOIL MAX

170

170

130

Default 180 - Use "FACTORY" Dip Switch to Adjust
Set same as BOIL DSGN

BOIL MIN

140

140

80

Default 140 - Use "FACTORY" Dip Switch to Adjust
Note:Some heating equipment may require a
minimum water temperature - ie fan coils

DLY

Not valid for Electric Boiler application

BOIL MASS

1

N/A

N/A

STG DLY

Au if PID in STGMODE

N/A

N/A

Minimum time between firing stages

DIFF

Au if PID in STGMODE

2

2

On or off of contact = 1/2 differential around target temp

STG DIFF

4

4

Temperature drop at which next stage turns on

ON DLY

1:00

1:00

Time before turning on next stage

OFF DLY

0:30

0:30

Time before turning off next stage

MIN ON

0:30

0:30

Minimum time stage is on before allowed to go off

MIN OFF

0:30

0:30

Minimum time stage is off before allowed to come on

PUMP DELAY

Off

Off

Off

WWSD
0 F

Caution:
"Factory" position on dip switch has to be returned to "Installer" position to prevent unauthorized changes to
Factory settings.

F or C

Field Entry Example for Mode 4 or Mode 5

Basic Monitron II and Minitron M3 Setup

Set the "MODE" to 1 or 2 if an outdoor Sensor is not used (1 = parallel piping, 2 = primary/secondary piping)

Baseboard System

4 or 5

no entry