Fig. 17 — 50PEC Unit Manual or Auto Changeover with Complete C Controller Wiring

Complete C

10

Complete C

LEGEND

NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 240-V (ORG) lead for

240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or
may have a circuit breaker.

4. FP1 thermistor provides freeze protection for

water. When using anti-freeze solutions, cut
JW3 jumper.

5. For remote sensor, position jumper J1 on upper

2 pins.

6. For metric display, position jumper on 1 pin.
7. Transformer secondary ground via GRN/YEL

wire from C to control box.

8. Mate-N-Lok† plug is optional.
9. See view A for wiring of units with water valve

(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).

10. Factory cut jumper (JW1). Dry contact will be

available between AL1 and AL2.

AL

—

Alarm Relay Contacts

BM

—

Blower Motor

BR

—

Blower Relay

CAP

—

Capacitor

CB

—

Circuit Breaker

CO

—

Sensor, Condensate Overflow

CR

—

Compressor Relay

DM

—

Damper Motor

ES

—

End Switch

FP1

—

Sensor, Water Coil Freeze Protection

FP2

—

Sensor, Air Coil Freeze Protection

HPS

—

High Pressure Switch

HPWS

—

High Presure Water Switch

JW1

—

Jumper Wire for Alarm

LOC

—

Loss of Charge Pressure Switch

PDB

—

Power Distribution Block

RAS

—

Return Air Sensor

RVS

—

Reversing Valve Solenoid

TRANS

—

Transformer

WV

—

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace
Option Low Voltage Wiring

*Optional wiring.
†Registered trademark of AMP Incorporated.

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lok

>>