Carrier 50PEC09-18 User Manual

Page 21

Advertising
background image

21

Fig. 20 — 50PEC Unit Manual or Auto Changeover and Deluxe D Controller

Deluxe D

9

Deluxe D

AL

— Alarm Relay Contacts

BM

— Blower Motor

BR

— Blower Relay

CAP

— Capacitor

CB

— Circuit Breaker

CO

— Sensor, Condensate Overflow

CR

— Compressor Relay

DM

— Damper Motor

ES

— End Switch

FP1

— Sensor, Water Coil Freeze Protection

FP2

— Sensor, Air Coil Freeze Protection

HPS

— High-Pressure Switch

HPWS

— High-Pressure Water Switch

JW4

— Jumper Wire for Alarm

LOC

— Loss of Charge Pressure Switch

NLL

— Night Low Limit Switch

PB

— Power Terminal Block

RAS

— Return Air Sensor

RVS

— Reversing Valve Solenoid

TRANS

— Transformer

WV

— Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace

LEGEND

*Optional wiring.

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 240-V (ORG) lead for

240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or may
have a circuit breaker.

4. FP1 thermistor provides freeze protection for

WATER. When using anti-freeze solutions, cut
JW3 jumper.

5. For remote sensor, position jumper J1 on upper

2 pins.

6. For metric display, position jumper on 1 pin.
7. Transformer secondary ground via GRN/YEL

wire from C to control box.

8. See view A for wiring of units with water valve

(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).

9. Factory cut jumper (JW4). Dry contact will be

available between AL1 and AL2.