Carrier 50PEC09-18 User Manual

Page 19

Advertising
background image

19

Fig. 18 — 50PEC Unit with Complete C and LON Controllers

Complete C

Complete C

LEGEND

*Optional wiring.

NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 240-V (ORG) lead for

240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or may
have a circuit breaker.

4. FP1 thermistor provides freeze protection for

water. When using anti-freeze solutions, cut JW3
jumper.

5. Low voltage wiring must be class 1 and voltage

rated equal or greater than unit supply voltage.

6. Factory cut jumper (JW1). Dry contact will be

available between AL1 and AL2.

7. Transformer secondary ground via GRN/YEL

wire from C to control box.

8. See view A for wiring of units with water valve

(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).

AL

—

Alarm Relay Contacts

BM

—

Blower Motor

BR

—

Blower Relay

CAP

—

Capacitor

CB

—

Circuit Breaker

CO

—

Sensor, Condensate Overflow

CR

—

Compressor Relay

DM

—

Damper Motor

ES

—

End Switch

FP1

—

Sensor, Water Coil Freeze Protection

FP2

—

Sensor, Air Coil Freeze Protection

FSS

—

Fan Speed Switch

HP

—

High-Pressure Switch

HPS

—

High-Pressure Switch

HPWS

—

High-Pressure Water Switch

JW1

—

Jumper Wire for Alarm

LOC

—

Loss of Charge Pressure Switch

LON

—

Local Operating Network

PB

—

Power Terminal Block

RVS

—

Reversing Valve Solenoid

TRANS —

Transformer

WV

—

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring
Option Low-Voltage Wiring
Printed Circuit Trace

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

Advertising