Installation – Vogelzang VG5770 User Manual

Page 10

Advertising
background image

10

G

VENT TERMINATION CLEARANCES:

A)

Minimum 4-foot (1.22m) clearance below or beside any door or window that opens.

B)

Minimum 1-foot (0.3m) clearance above any door or window that opens.

C)

Minimum 3-foot (0.91m) clearance from any adjacent building.

D)

Minimum 7-foot (2.13m) clearance from any grade when adjacent to public walkways.

E)

Minimum 2-foot (0.61m) clearance above any grass, plants, or other combustible materials.

F)

Minimum 3-foot (0.91m) clearance from an forced air intake of any appliance.

G)

Minimum 2-foot (0.61m) clearance below eves or overhang.

H)

Minimum 1-foot (0.3m) clearance horizontally from combustible wall.

I)

Must be a minimum of 3 foot (0.91m) above the roof and 2 foot (0.61m) above the highest point or the roof within

10 feet (3.05m).

FIGURE 6

VENT TERMINATION CLEARANCES

Installation