Installation – Vogelzang VG5770 User Manual

Page 12

Advertising
background image

12

NOTE: Dimensions from the fl oor to your stoves
inlet/exhaust pipes are approximate and may vary
depending on your installation.

FIGURE 9

TYPICAL FRESH AIR TERMINATION

FIGURE 8

EXHAUST/INLET LOCATIONS

OUTSIDE AIR SUPPLY

(optional, unless installing in a mobile home)

Adequate ventilation air is required to operate this heater. During operation, the heater draws air for combustion which
can be assisted by the installation of outside combustion air inlets. However, certain weather conditions such as icing or
use of kitchen exhaust fans may impact and reduce the effectiveness of vents. It is important to note that room air starva-
tion will negatively impact the operation of the heater.

Depending on your location and home construction, outside air may be necessary for optimal performance.
Metal pipe (solid or fl exible) must be used for the outside air installation. PVC pipe is NOT approved and should NEVER
be used.
A wind shield over the termination of the outside air pipe or a 90-degree elbow or bend away from the prevailing winds
MUST be used when an outside air pipe is installed through the side of a building. The outside air termination MUST
be at least 1ft (0.305m) away from the exhaust system termination.
The outside air pipe on your heater is 2” (50.8mm) OD. The outside air connecting pipe must be at least 2” (50.8mm) ID.
The outside air connection used MUST NOT restrict the amount of air available to your heater. The outside air connecting
pipe must be as short and free of bends as possible, and it must fi t over, not inside, the outside air connection to the heater.

SPECIAL MOBILE HOME REQUIREMENTS



WARNING! - DO NOT INSTALL IN A SLEEPING ROOM



CAUTION! - THE STRUCTURAL INTEGRITY OF THE
MOBILE HOME FLOOR, WALL, AND CEILING/ROOF
MUST BE MAINTAINED.

In addition to the previously detailed installation requirements,

mobile home installations must meet the following

requirements:

• The unit must be secured to the fl oor using lag bolts in

the holes provided in the pedestal base.

• The heater must be electrically grounded to the steel

chassis of the mobile home with 8 GA copper wire using

a serrated or star washer to penetrate paint or protective

coating to ensure grounding.

• Vent must be 3 or 4-inch “PL” Vent and must extend a

minimum or 36 in.(914mm) above the roof line of the

mobile home and must be installed using a UL listed

ceiling fi re stop and rain cap.

• When moving your mobile home, all exterior venting must

be removed while the mobile home is being relocated.

After relocation, all venting must be reinstalled and

securely fastened.

• Outside Air is mandatory for mobile home installation. See Outside Air Supply section and your dealer for purchasing.
• Check with your local building offi cials as other codes may apply.

Installation

Mobile Home Mounting

Bolt Holes

Mobile Home

Mounting Bolt Holes