Connecting the loads, Applying the loads – Winco EC22000/A User Manual

Page 9

Advertising
background image

7

60706-23

224-00

slightly lower voltage when the generator is loaded

to its full capacity than when running no load. The

slight variation in speed also affects the frequency of

the output current. This frequency variation has no

appreciable effect in the operation of motors, lights

and most appliances. However, electronic equip-

ment and clocks will be affected if correct RPM is not

maintained. See Load vs. Output chart.

Although individual units and models vary slightly,

the normal voltage and frequency of the engine-gen-

erator described in this manual are approximately as

follows, under varying loads:

LOAD VS. OUTPUT

Generator

Load

Speed

(RPM)

Frequency

(Hz)

Voltage

None

3690

61.5

125V

Half

3600

60.0

120V

Full

3510

58.5

115V

The speed of the engine was carefully adjusted at

the factory so that the generator produces the proper

voltage and frequency. For normal usage, the speed

setting should not be changed. If the generator

is being run continuously on a very light load, it is

often advisable to lower the operating speed slightly.

Whenever making any speed adjustments check the

unit with a voltmeter or tachometer and be sure the

speed is correct.

Lower voltage may damage both the generator and

any load connected to it. Running the engine at ex-

cessively high speeds results in high voltage, which

may significantly shorten the life of appliances being

used.

Output voltage should be checked periodically to

ensure continued proper operation of the generat-

ing plant and appliances. If the generator is not

equipped with a voltmeter, it can be checked with a

portable meter. Frequency can be checked by using

an electric clock with a sweep second hand. Timed

against a wrist watch or a stop watch, the clock

should be correct within +/- 2 seconds per minute.

CONNECTING THE LOADS

CAUTION: EQUIPMENT DAMAGE

Failure to properly limit and balance the load applied

to the generator will cause the generator to produce

low voltage and may damage the engine generator

set. It may also cause severe damage to the loads

connected to the generator at that time. Improper

loading of the generator set constitutes abuse and

will not be covered by warranty.

A 60 amp receptacle (NEMA 14-60) has been pro-

vided to allow the connection of loads to the gen-

erator on the EC8000. This receptacle is a 4 wire

full load receptacle protected by a 60 amp breaker

mounted in the control box on top of the generator.

On the EC22000 the load wiring must be wired

directly in the 80 amp breaker mounted in the control

box on the top of the generator When wiring directly

to the circuit breaker in the box be sure to connect a

neutral wire and ground wire to the appropriate loca-

tions in the control box.

Your individual loads must be protected by individual

circuit breakers mounted in some type of distribution

panel. This location will also be where you will in-

stall your neutral to ground bond. You must wire four

separate wires from the generator (2 -hot,- neutral

and 1-ground) to the distribution panel.

APPLYING THE LOADS

Allow the engine to warm up for two or three minutes

before applying any load. This will allow the engine

to reach normal operating temperature and oil to

circulate throughout the engine. A short warm-up

time will permit the engine to work more efficiently

when the load is applied and will reduce the wear in

the engine, extending its life.

If a large motor is being started or multiple motors

are being started, they should be started individually

and the largest should be started first.

CAUTION: EQUIPMENT OVERLOAD

Keep the generator load within the generator and

receptacle nameplate rating. Overloading may

cause damage to the generator and/or the loads .

Most electric tools and appliances will have the volt-

age and amperage requirements on their individual

Advertising
This manual is related to the following products: