A caution, Step 6 — install venting, Caution – Carrier 48NLT User Manual

Page 6: Step 7 — install gas piping

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

r MIN

Condensate water can be drained directly onto the roof in

rooftop installations (where permitted) or onto a gravel apron
in ground-level installations. When using a gravel apron,

make sure it slopes away from the unit.

Step 6 — Install Venting

— The vent cap assembly

is shipped in the burner compartment. Remove the access
door to locate the assembly.

A

CAUTION

The venting system is designed to ensure proper vent­

ing. The vent cap assembly must be installed as indi­
cated in this section of the unit Installation Instructions.

NOTE; Screw holes in the flue assembly and the unit flue
panel are

not

symmetrically located. Make sure they are

oriented properly when installing these components.

Refer to Fig. 6 and install the vent cap as follows:

1. Place vent cap assembly over flue panel. Orient screw

holes in vent cap with holes in flue panel.

2. Secure vent cap in place by inserting the single screw on

the right side of vent cap.

3. Place the vent cap guard over the vent cap. Orient holes

in vent cap guard with holes in vent cap and flue panel.

4. Secure the entire assembly with the remaining 2 screws

on the left side of vent cap and vent-cap guard
assembly.

Step 7 — Install Gas Piping

— The gas supply pipe

enters the unit through the access hole provided. The gas
connection to the unit is made to the Vi-in. FPT gas inlet on
the manual shutoff or gas valve.

Install a separate gas supply line that runs directly from

the meter to the heating section. Refer to Table 2 and the
National Fuel Gas Code (NFGC) for gas pipe sizing.

Do

not use cast-iron pipe.

It is recommended that black iron

pipe is used. Check the local utility for recommendations
concerning existing lines. Choose a supply pipe that is large
enough to keep the pressure loss as low as practical.

Never

use pipe smaller than the ‘A-in. FPT gas inlet on the unit

gas valve.

For natural gas applications, the gas pressure at unit gas

connection must not be less than 5 in. wg or greater than

13 in. wg while the unit is operating. For propane applica­

tions, the gas pressure must not be less than 11 in. wg or
greater than 13 in. wg at the unit connection.

When installing the gas supply line, observe local codes

pertaining to gas pipe installations. Refer to the NFGC ANSI

(American National Standards Institute) Z223.1-1988 NFPA
(National Fire Protection Association) 54-1988 (in Canada,
CAN/CGA [Canadian Gas Association] B 149.1, (2)-M86).
In the absence of local building codes, adhere to the fol­
lowing pertinent recommendations:

1. Avoid low spots in long runs of pipe. Grade all pipe

V4

inch in every 15 ft to prevent traps. Grade all hori­

zontal runs downward to risers. Use risers to connect to
heating section and to meter.

2. Protect all segments of piping system against physical

and thermal damage. Support all piping with appropri­
ate straps, hangers, etc. Use a minimum of one hanger

every 6 ft. For pipe sizes larger than

Уг

in., follow rec­

ommendations of national codes.

3. Apply joint compound (pipe dope) sparingly and only to

male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.

Never use Teflon tape.

4. Install sediment trap in riser leading to heating section.

This drip leg functions as a trap for dirt and condensate.
Install trap where condensate cannot freeze. Install this
sediment trap by connecting a piping tee to riser leading
to heating section, so that straight-through section of tee
is vertical. See Fig. 7. Then, connect capped nipple into
lower end of tee. Extend capped nipple below level of
gas controls.

Table 2 — Maximum Gas Glow Capacity*

NOMINAL

IRON PIPE,

SIZE

(in.)

INTERNAL

DIAMETER

(In.)

LENGTH OF PIPE, FTf

10

20

30

40

50

60

70

80

90

100

125

150

175

200

V2

.622

175

120

97

82

73

66

61

57

53

50

44

40

%

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

VA

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

VA

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

‘Capacity of pipe in cu ft of gas per hr for gas pressure of 0 5 psig or less. Pressure drop of 0.5 in. wg

(based on a 0.60 specific gravity gas) Refer to Table C-4, NFPA 54-1984

fThls length includes an ordinary number of fittings

Advertising
This manual is related to the following products: