Table 5 — Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating input

NOMINAL SIZE

HEATING

UNIT TEMPERATURE RISE (T)

INPUT (Btuh)

20

25

30

35

40

45

50

55

60

65

70

75

80

NLT018,024,030

40,000

-

-

987

846

740

658

592

538

493

-

-

-

-

NHT024; NMT030

60,000

-

-

-

-

-

987

888

808

740

683

634

592

-

NLT036,042

60,000

-

-

1481

1269

1111

987

888

808

740

-

-

-

-

NHT030; NMT036,042

80,000

-

-

-

-

-

1316

1185

1077

987

911

846

790

-

NLT048

80,000

-

2370

1975

1693

1481

1316

1185

1077

-

-

-

-

-

NLT060

80,000

2962

2370

1975

1693

1481

1316

1185

-

-

-

-

-

-

NET036,042

96,000

-

-

-

-

1777

1580

1422

1292

1185

1096

1015

-

-

NHT036,042; NMT048

100,000

-

-

-

2116

1851

1646

1481

1346

1234

1139

-

-

-

NMT060

100,000

-

-

2469

2116

1851

1646

1481

1346

1234

-

-

-

-

NVT036,042; NHT048

120,000

-

-

-

-

-

-

1777

1616

1481

1367

1269

1185

1111

NHT060

120,000

-

-

-

2539

2222

1975

1777

1616

1481

1367

-

-

-

NVT048,060

144,000

-

-

-

-

-

2370

2133

1939

1777

1641

1523

1422

-

f

NOTE: Dashed areas of the table do not fall In the approved temperature rise range of the unit

Table 6 — Superheat Charging Table*

TEMP (F)

50

52

54

56

58

60

62

64

66

68

70

72

74

76

55

9

12

14

17

20

23

26

29

32

35

37

40

42

45

60

7

10

12

15

18

21

24

27

30

33

35

38

40

43

65

6

10

13

16

19

21

24

27

30

33

36

38

41

70

-

-

7

10

13

16

19

21

24

27

30

33

36

39

75

-

6

9

12

15

18

21

24

28

31

34

37

80

-

-

-

-

5

8

12

15

18

21

25

28

31

35

85

-

-

-

-

-

-

8

11

15

19

22

26

30

33

90

-

-

5

9

13

16

21

24

27

31

95

-

-

-

-

-

-

-

6

10

14

18

22

25

29

100

-

-

-

-

-

-

-

-

8

12

15

20

23

27

105

-

-

-

-

-

-

-

-

5

9

13

17

22

26

110

-

-

-

-

-

-

-

-

-

6

11

15

20

25

115

-

-

-

-

-

-

-

-

-

-

8

14

18

23

•Superheat at suction service valve.
NOTE: Do not attempt to charge system under these conditions; refrigerant slugging may occur

Table 7 — Required Suction-Tube Temperature (F)*

TEMP (F)

61.5

64.2

67.1

70.0

73.0

76.0

79.2

82.4

85.7

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

16

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

32

67

69

71

73

75

77

79

81

83

34

69

71

73

75

77

79

81

83

85

36

71

73

75

77

79

81

83

85

87

38

73

75

77

79

81

83

85

87

89

40

75

77

79

81

83

85

87

89

91

•Temperature at suction service valve