Carrier 48NLT User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WT

CORNER WT LB/KG

LB

KG

A

B

C

D

48NHT036

208/230/1/60, 208/230/3/60, 460/3/60

530

241

117/53

147/67

148/67

118/54

48NVT036

208/230/1/60, 208/230/3/60, 460/3/60

536

243

119/54

148/67

149/68

120/54

48NHT042

208/230/1/60, 208/230/3/60, 460/3/60

550

249

122/55

152/69

153/69

123/56

48NVT042

208/230/1/60, 208/230/3/60. 460/3/60

556

252

124/56

153/69

154/70

125/57

48NLT048

208/230/1/60, 208/230/3/60, 460/3/60

574

261

128/58

158/72

159/72

129/59

48NMT048

208/230/1/60, 208/230/3/60, 460/3/60

580

263

130/59

159/72

160/73

131/59

48NHT048

208/230/1/60, 208/230/3/60, 460/3/60

586

265

131/59

161/73

162/73

132/60

48NVT048

208/230/1/60, 208/230/3/60, 460/3/60,

586

265

131/59

161/73

162/73

132/60

48NLT060

208/230/1/60, 208/230/3/60, 460/3/60

604

274

136/62

165/75

166/75

137/62

48NMT060

208/230/1/60, 208/230/3/60, 460/3/60

610

277

138/63

166/75

167/76

139/63

48NHT060

208/230/1/60, 208/230/3/60, 460/3/60

616

280

139/63

168/76

169/77

140/64

48NVT060

208/230/1/60, 208/230/3/60, 460/3/60

616

280

139/63

168/76

169/77

140/64

NOTE. Clearances must be maintained to prevent recirculation of air from

condenser-fan discharge.

REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL - in. (mm)
Maximum Extension of Overhang

48(1219.2)

Unit Top

........................... ■ .36(914.4)

Duct Side of Unit .

.

.

.

.

6 Min. (152.4 Min.)

Side Opposite Ducts

.30 (762.0)

Bottom of Unit. .

.

.

.

.

0

REQUIRED CLEARANCES FOR SERVICING - in. (mm)

Blower Access Panel Side ...

.

30 (762.0)

Control Box Access Side

. .

30 (762.0)

Fig. 3 — 48 Dimensional Drawing, Sizes NHT036 — NVT060