Table 3 — electrical data – Carrier 48NLT User Manual

Page 9

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 3 — Electrical Data

UNIT

SIZE

NOMINAL

V-PH-HZ

MODEL NO.

48

VOLTAGE

RANGE

COMPR

CONDENSER-

FAN MOTOR

EVAPORATOR-

FAN MOTOR

AWG MIN

WIRE SIZE

POWER SUPPLY

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP

01B

208/230-1-60

NLT018

187

253

82

49 0

08

2.5

14

13 6

20

024

208/230-1-60

NLT024
NHT024

187

253

11.6
11.6

61 0
61.0

08

2.5

12

17 1

25

030

208/230-1-60

NLT030
NMT030
NHT030

187

253

14.3

86.0

08

25
25

3.0

10

21 2
21.2
21 7

30

036

208/230-1-60

NLT036
NMT036
NET036
NHT036
NVT036

187

253

21 1

100 0

1 5

30

3.0

45
45
45

8

30.9
30 9
32.4
32 4
32.4

40

208/230-3-60

NLT036
NMT036
NET036
NHT036
NVT036

187

253

14.7

67.0

1 9
1.9
1.9

22
22

30
30
45
45
45

10

23.3
23 3
24 8
25 1
25 1

30

460-3-60

NLT036
NMT036
NET036
NHT036
NVT036

414

506

7 1

34 0

1.2

1 5
1 5
23
23
23

14

11 6
11 6
124
124
12.4

15

042

208/230-1-60

NLT042
NMT042
NET042
NHT042
NVT042

187

253

23.9

95.4

1 5

3.0
3.0
45
45
4.5

8

34 3
34 3
35 9
35.9
35 9

50

208/230-3-60

NLT042
NMT042
NET042
NHT042
NVT042

187

253

15.3

82 0

1.9
1 9
1 9
2.2
2.2

30
3.0
45
4.5
4.5

10

24 0
24.0
25 5
25.8
25 8

35
35
40
40
40

460-3-60

NLT042
NMT042
NET042
NHT042
NVT042

414

506

77

41 0

1 2

1 5
1 5

23
23
2.3

14

123
12.3
13 1
13.1
13 1

20

048

208/230-1-60

NLT048
NMT048
NHT048
NVT048

187

253

26 5

1140

2.1

4.5

45

4.5

8

39 7
39 7
39.7

60

62

6

41 4

208/230-3-60

NLT048
NMT048
NHT048
NVT048

187

253

16.8

84 0

22

45
45
4.5
62

10

27.7
27 7
27 7
29 4

40

460-3-60

NLT048
NMT048
NHT048
NVT048

187

253

82

42 0

1 2

23
23
2.3
32

14

13.8
138
138
147

20

060

208/230-1-60

NLT060
NMT060
NHT060
NVT060

187

253

30 7

135 0

2 1

62

6

46 7

60

208/230-3-60

NLT060
NMT060
NHT060
NVT060

187

253

21 4

130 0

22

6.2

8

35 5

50

460-3-60

NLT060
NMT060
NHT060
NVT060

414

506

104

55 0

1 2

32

12

17.4

25

AWG
FLA
LRA
MCA
MOCP
NEC
RLA
NOTES:
1

American Wire Gage
Full Load Amps
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Rated Load Amps

In compliance with NEC requirements for multimotor and combination load
and equipment (refer to NEC Articles 430 and 440), the overcurrent pro­

tective device for the unit shall be fuse or HACR breaker

Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2% Use the following formula to determine the % voltage imbalance.
% Voltage Imbalance

_ y max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 452 volts

Determine maximum deviation from average voltage.

(AB) 457 - 452 =5 volts

(BC) 464 - 457 =7 volts

(AC) 457 - 455 =2 volts

Maximum deviation is 7 volts.

Determine % voltage imbalance

% Voltage Imbalance =100 x

7

"457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%

IMPORTANT: If the supply voltage phase imbalance is more than 2%,

contact your local electric utility company immediately

BC = 464 volts
AC = 455 volts

Average Voltage

452 + 464 -r 455

3

1371

—JT— =457