Carrier 48NLT User Manual
Page 21
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 11 — Heating Troubleshooting Chart
SYMPTOM
CAUSE
REMEDY
IGN locked out.
LED flashing
Look for problems external to the ignitor module.
LED glowing continuously
Replace IGN control.
Pilot will not light.
No spark at electrode
Check air gap between electrode tip and pilot target
Gap should be as shown in Fig. 15.
Readjust as necessary.
Clean moisture or dirt accumulation on electrode ceramic with
cloth.
Cracked ceramic — replace pilot electrode assembly
Check for loose or broken wiring at and between electronic
control head and electrode Replace wire or tighten connection
as necessary.
Check fuses or circuit breaker to ensure voltage to unit.
Check for 24 v between TH and COM. If you read 24 v and
above steps have been completed, replace electronic ignition
control.
Spark shorting out to main burner
Realign electrode tip away from main burner but maintain
spark gap to pilot burner. See Fig. 15.
No gas at pilot burner
Clean pilot orifice.
Check inlet pressure to gas value. Recommended operating
pressure 7-in. wg natural gas, 11-in. wg LP gas; 0.5 psig (13.6-
in. wg) max. pressure
Check for 24 v between terminals PV and COM If you read 24
V and above steps have been completed, replace gas valve.
Burners will not ignite.
Water in gas line
Drain — install water trap.
No power to furnace
Check power supply, fuses, wiring or circuit breaker.
No 24-v power supply to control circuit
Check transformer — replace if necessary.
Miswired or ioose connections
Check all wiring and wirenut connections.
Dirty pilot — yellow flame
Clean pilot orifice.
Pilot burning improperly — sharp blue flame
Replace pilot.
Burned-out heat anticipator in thermostat
Replace thermostat.
No gas at main burners
1. Check for 24 v between terminals MV and COM on control
head If you read 24 v, replace gas valve portion of control
head/gas valve assembly.
2. If 24 V is not present, check flame sensor for cracked ce
ramic insulator or shorted sensor cable.
Broken thermostat wire
Run continuity check to locate break.
Inadequate heating.
Dirty air filter
Clean or replace filter as necessary.
Gas input to furnace too low
Check gas pressure at manifold. Clock gas meter for input. If
loo low, increase manifold pressure, or replace with correct
orifices.
Unit undersized tor application
Replace with proper unit — or add additional unit
Restricted airflow
Clean or replace filter — or remove any restriction.
Blower speed too low
Use faster speed tap
Check temperature rise.
Limit switch cycles main burners
Dirty air filters — clean or replace.
Registers closed, restricted ductwork — open or remove
restriction.
Check temperature rise.
Check heat anticipator setting on thermostat — readjust.
Poor flame
characteristics.
Incomplete combustion results in;
Aldehyde odors, CO, sooting flame —
floating flame
Check all screws around flue outlets and burner compartment
— tighten.
LACK OF COMBUSTION AIR.
Cracked heat exchanger — replace.
Overfired furnace — reduce input, or change orifices.
Check vent for restriction — clean as required
Check orifice for burner alignment.
#
#
GR
— Ground
LP
— Liquid Propane
21