Indoor coil – Carrier 50YQ User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

11. Clean system. Add new suction line filter-drier

as described below.

NOTE: If a compressor failure was caused by

motor winding burnout, the by-products of the
burnout must be separated from the circulating
refrigerant. This must be done before the by­

products enter the reversing valve or accumu­

lator and render parts inoperative. Burnout by­

products can cause future system operating
problems if left in the system.

Clean the system by installing a suction line

drier in the refrigerant line where the suction gas
enters the reversing valve. During the cooling
cycle, this is the line from the indoor coil run­
ning across the top of compressor compart­
ment; during heating cycle, install drier in line

between outdoor coil and reversing valve. If

possible, run unit in cooling mode when clean­

ing system as installation of temporary suction
drier is simplified.

For drier installation during heating cycle, cut
vertical line below reversing valve to install

fittings and tubing as suction drier must be

placed outside of cabinet. Fabricate and install a

temporary access panel to provide protection

against entry and possible electric shock hazard.

-> To provide protection for the reversing valve,

do not place filter-drier between reversing valve
and accumulator. Since the suction drier works
on one mode only, temporarily wire the unit in

the selected mode (heating or cooling, based on

suction drier location). To insure cooling opera­

tion only, install a jumper between terminals

“R” and “O” on the low voltage terminal board.
For heating operation only, remove and insulate

one of the reversing valve solenoid leads. Run
unit for 48 hours and check oil for acidity. If
satisfactory, remove suction line drier. Refer to
and follow procedure under AccuRater™ Ser­
vicing for cleaning of AccuRater. Rewire unit

to normal condition.

12. Triple-evacuate and recharge unit. See Refrig­

erant Charging.

Filter-Drier

— Install an accessory 50YQ900001

reversible, liquid line filter-drier assembly. Remove
dual piston AccuRater — save pistons. Cut 11 in.
from liquid line. Install flare nut on new end of line
and flare line. Install new strainers from accessory
package. Following the instructions in accessory
package, install filter-drier package components.

NOTE; Follow instructions carefully as AccuRater
piston locations are reversed from those shown
when a filter-drier is not used. On model 50YQ060,
install filter-drier and AccuRater in a vertical
position.

Lubrication

COMPRESSOR contains factory oil charge. Re­
place oil when lost. See Table 5 for oil recharge. If

necessary, refer to Carrier Standard Service Tech­

niques Manual, Chapter 1, Refrigerants, page 1-21,
for oil recharging procedure. Use Carrier PP33-1,
Texaco Capella B or Suniso 3G oil.

■ FAN MOTOR BEARINGS are prelubricated for 3

years heavy duty or 5 years normal duty. If oiling

holes are provided at each end of fan motor, remove
fan motor and lubricate motor with 32 drops (16
drops per hole) of SAE 10 nondetergent oil at
intervals described below;

a.

Annually, when environment is very dirty,

ambient temperature is higher than 105 F and
average unit operating time exceeds 15 hours
a day.

b. Every 3 years when environment is reasonably

clean, ambient temperature is less than 105 F and
unit operating time averages 8 to 15 hours a day.

c.

Every 5 years when environment is clean,

ambient temperature is less than 105 F and
unit operating time averages less than 8 hours
a day.

Indoor Coil

CAiniOJ?' Before petjibri33S(ng;

marntmance».

isr

tamed

TOP COVER

INDOOR COIL

Fig. 24 — Fan, Top Cover, Coil Details

Lift or remove unit top cover for access to indoor

coil. See Fig. 24. Inspect coil periodically. Clean as
described under Outdoor Coil below.

Condensate Drain

— Clean condensate drain trap

with bottle brush; then flush condensate pan be­
neath indoor coil with clean water. Ensure water

flows freely thru condensate drain.

^Indoor Fan Assembly

(Fig. 25) — Fan wheel

should be centered in fan housing. To adjust fan,
remove as follows;

1. Disconnect motor wires.

2. Remove sheet metal screws holding assembly in

place.

3. Slide entire fan assembly out of unit.

4. Loosen setscrew securing wheel to motor shaft.

5. Adjust wheel and tighten setscrew.