Table 4 — Service Data

UNIT 50YQ

024

030

036

042

048

060

R-22 CHARGE* (lb)

54

5 7

5 15

6 7

7 3

8 6

Refrig Control

AccuRater^M

INDOOR FAN

Centrifugal — Direct Drive — 3-Speed

Rpm

1100/1050/900

Diameter (in.)

9

9

9

10

10

10

Width (in.)

7

7

9

9

9

10

Range (cfm)

833-1040

1000-1250

1183-1480

1367-1708

1633-2040

1800-2250

Motor Hp

1/5

1/5

1/3

1/2

1/2

3/4

OUTDOOR FAN

Propeller — Direct Drive

Cfm

2500

2500

2500

2700

3200

3600

Rpm

1050

1050

1050

1050

1050

1050

Diameter (in.)

20

20

20

20

20

20

Motor Hp

1/5

1/5

1/4

1/4

1/4

1/4

"Factory refrigerant charge

Unit refrigerant system is factory charged. When

recharging is necessary, weigh in total charge indi­
cated in Table 4. (Charge must be weighed in during

heating season.) Remove any refrigerant remaining
in system before recharging. If system has lost com­
plete charge, evacuate system to 500 microns

(29.7 in. vacuum) before recharging. Service port
connections are provided on unit suction and dis­
charge lines for evacuation and charging. (See

Fig. 10 for service port location.) Dial-a-charge

charging cylinder is an accurate device used to re­
charge systems by weight. These eylinders are avail­
able at refrigeration supply firms.

OUTDOOR FAN

DISCHARGE GRILL

CONTROL WIRING
TERMINAL BLOCK

TOP COVER

UNIT CONTROL
BOX

REVERSING
VALVE

\

INDOOR

INDOOR BLOWER

COIL

MOTOR I

CONTROL WIRING

CONDUIT

SUCTION LINE'
SCHRADER
FITTING

COMPRESSOR
HOLD DOWN
BOLTS

ELECTRIC

COMPRESSOR

a

I

s

EMBLY

CONDENSATE

\

DRAIN LINE LINEWIRING

SPLICE BOX

Fig. 10 — Component Location (Typical)

To check and/or adjust charge during cooling

season, use correct Cooling Cycle Charging Chart
(Fig. 11 thru 16) and follow Charging Chart Method
below. The charging chart may also be used as an
alternate method of recharging system.

To check system operation during heating cycle,

use correct Heating Cycle Operation Check Chart
(Fig. 17 thru 22). These charts indicate whether a
correct relationship exists between system operating
pressures and air temperatures entering unit. If

pressure and temperature lines do not intersect on
chart, the system refrigerant charge may not be cor­
rect or other sysem abnormalities may exist. Do not

use Operation Check Charts to adjust refrigerant

charge. Weigh charge into system.

COOLING CYCLE CHARGING CHART

METHOD

1. Operate unit a minimum of 10 minutes before

checking

charge,

and

after

each

charge

adjustment.

2. Measure suction pressure by attaching a gage to

unit suction service port. (See Fig. 10 for correct
service port location.)

3. Measure outdoor (coil inlet) air dry-bulb tem­

perature. Use service thermometer.

4. Using a sling psychrometer, measure wet-bulb

temperature of air entering indoor fan coil.

5. Refer to correct Charging Chart. Locate on

curves where outdoor air dry-bulb and indoor
air wet-bulb temperature lines intersect.

6. From intersect point, project vertically down­

ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure
(Step 2).

7. If unit suction pressure is lower than ehart

pressure, add refrigerant to system until chart
pressure is reached. If unit suction pressure is
higher than chart pressure, remove refrigerant
until chart pressure is reached.

7 8 1