Start-up, I-r' tv – Carrier 50YQ User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 2 — Unit Electrical Data (60-Hz)

i-r'

tv

OPER

COMPRESSOR

IFM

OFM

BRANCH CIRCUIT

VOLTAGE*

Min

Max

Ft

Wire

Min Gnd

Max Fuse

Min

Circuit

Amps

MODEL

V/PH

Max

Min

LRA

RLA

BCSC

FLA

FLA

Wire

Size

Wire

Size

or HACR

Type Ckt»*

(AWG)t

(AWG)t

Bkr Amps

50YQ024

66

154

2 4

1 3

10

48

}— -1

35

23 0

50YQ030

72

16 1

24

1 3

10

46

10

35

23 8

^ 50YQ036

230/1

253

207

88

18 2

3 6

2 1

10

38

10

45

28 5

50YQ042

94

21.0

21 2

49

1 9

8

52

10

50

33 3

50YQ048

106

25 0

27 9

49

2 2

6

71

10

60

42 0

50YQ060

208/230/1

253

187tt

150

29 2/33 4

35 3

6 4

20

4

43

6

60

52 5

50YQ042

200/3

220

180

79

146

16 6

49

20

10

55

10

40

27 6

50YQ048

87

16 9

183

49

2 2

10

48

10

45

30 0

50YQ036

200/230/3

253

180

87

12 5/11 7

3 6

2 1

10

74

10

30

21.3/25 3

50YQ042

230/3

253

207

g

T~

U6

143

49”

i¥~

67

id

24 7

50YQ048

70

14 8

16 4

4 9

2 2

10

58

10

40

27 6

50YQ042

460/3

506

414

35

g 3

49

1 9 ‘

14

104

14

15

12 4

50YQ048

35

7.5

8 8

4 9

2 2

14

90

12

20

14 6

50YQ042

575/3

632

518

27

49

6 8

49

1 9

14

164

14

15

11 2

50YQ048

30

60

64

49

2 2

14

141

14

15

10 9

AWG

BCSC
FLA
IFM
LRA
OFM
RLA

American Wire Gage

Branch Circuit Selection Current
Full Load Amps
Indoor Fan Motor
Locked Rotor Amps
Outdoor Fan Motor
Rated Load Amps

HACR — Heating Air Conditioning & Refrigeration

ELECTRIC HEATER INSTALLATION — For

complete heater installation data, refer to accessory
electric heater Installation, Start-Up and Service

Instructions.

GROUND LUG

(IN SPLICE BOX)

l-PHASE
CONN
TO
DISCONNECT

PER NEC

--GROUND LEAD-

Ll

L2

________________

________________

^Permissible limits of the voltage range at which units will operate

satisfactorily

tCopper wire sizes based on 60 C Use copper or copper-clad aluminum wire

only Use latest NEC for copper-clad aluminum conductor sizing

^Required when using nonmetallic conduit

“Maximum dual element fuse
ttMinimum voltage is 197 when outdoor ambient temperature exceeds

105 F

Heat Anticipator Settings for Room Thermo­

stat

— Set anticipator settings for room thermostat

according to Table 3. These settings may be changed
slightly to provide a greater degree of comfort for a
particular installation.

Table 3 — Thermostat Anticipator Setting

BLK-----------(

-YEL----------

i

50YQ HEAT PUMP

GROUND LUG

(IN SPLICE BOX)

UNIT

50YQ024,

030,036,
042,048,

060

FIRST STAGE

ANTICIPATOR

SETTING

Fixed

ACCESS.

ELECTRIC

HTR (Kw)

240 V 280 V

5 0

3 75

7 5

5 6

100

7 5

15 0

11 3

20 0

150

25 0

188

27 0

22 25

SECOND STAGE

ANTICIPATOR

SETTING

-gg—

26
26
52
52
52
78

3-PHASE
CONN

TO
DISCONNECT

PER NEC

------ GROUND LEAD-

LI----------------------------------------------

L2-

L3

______________________________ -YPl------------------------

■ -^-BLK--

BLU-----------

i

-YEL------------ i

50YQ HEAT PUMP

_____ Field Wiring

Splice Connections

NOTE Use copper or copper-clad aluminum wire

Fig. 7 — Line Power Connections

START-UP

The 50YQ unit compressors are equipped with

crankcase heaters. It is recommended that heater be
energized a minimum of 24 hours before starting unit.
To energize heater only, set thermostat at OFF posi­
tion; turn on unit main power at disconnect switch.

Accessory Outdoor Thermostat

provides adjust­

able outdoor control of accessory electric heaters
of 15 Kw and over. This thermostat makes contact
when a drop in outdoor temperature occurs. It ener­
gizes a stage of electric heat when the outdoor tem­
perature setting is reached, provided the room

thermostat is on the second stage of heating. One
outdoor thermostat is recommended for each stage
of electric heat after the first stage. Set the outdoor

thermostat(s) progressively lower for each stage.

Refer to heat load of building and unit capacity to

determine the correct outdoor thermostat settings.

The accessory emergency heat relay is required

when 2 outdoor thermostats are used. It is auto­
matically energized by the manually operated emer­
gency heat switch in the indoor thermostat subhase.

The indoor thermostat locks out compressor and the
relay bypasses the outdoor thermostats for electric
heater operation during heat pump shutdown.
When one outdoor thermostat is used, an emergency
heat relay is not required. The emergency heat
switch in the indoor thermostat subbase bypasses
outdoor thermostat, locks out compressor and acti­
vates electric heater.