Floor may be combustible, Figure 5, Warning – Carrier UPFLOW 58BTA User Manual

Page 12: Air-flow data, Minimum clearance to combustibles

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

MINIMUM CLEARANCE TO COMBUSTIBLES

(Adequate service clearance should be provided over and above these dimensions, as required.)

CLEARANCE FROM :

UPFLOW

HORIZONTAL

Top of furnace casing or plenum

2"

2"

Top of horizontal warm-air duct within 6 ft of furnace

2"

3"

Flue pipe, measured horizontally or below pipe

9"

9"

Flue pipe, measured vertioally above pipe

9"

9"

Any side of supply plenum and warm-air duct within 6 ft of furnace

1"

1"

Front of furnace

24

"

24"

Sides of furnace

2

"

2"

Rear of furnace

2"

2"

Bottom of furnace

0"*

0"*

Floor may be combustible

Figure 5

WARNING

When operating the furnace in the heating mode, the static pressure and the temperature rise (supply air
temperature minus return air temperature) must be within those limits specified on the rating label. Failure to follow
this warning could lead to severe furnace damage.

AIR-FLOW DATA

UNIT OUTPUT

(KBTUH)

BLOWER
SPEED

EXTERNAL STATIC

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

150 and 200

(12 X 12 WHEEL)

(3/4 HP MOTOR)

LOW

1640

1590

1540

1515

1460

1410

1350

1275

1190

1075

MED

2195

2125

2060

1990

1915

1860

1785

1700

1620

1525

HIGH

2485

2395

2305

2250

2145

2075

1975

1885

1780

1675

NOTES:

1) . AIR FLOW VALUES IN CUBIC FEET PER MINUTE (CFM), ROUNDED TO NEAREST FIVE (5) CFM

2) . DATA TAKEN WITHOUT FILTERS IN PLACE

Figure 6