Carrier 38HQ User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Since it is lightweight, the outdoor unit can be

mounted on a platform attached to or built out from

structure. Construct platform using drainage and

clearance recommendations above. Locate and con­

struct platform to avoid possible transfer of unit

vibration to structure.

ON THE ROOF: MOUNT OUTDOOR COIL ON

A LEVEL PLATFORM OR FRAME. Unit must

be

elevated

for

proper

clearance

as

described

under ground installation above. Roof design and
water drainage must be planned to prevent units
from setting in water. Flash all roof openings to

prevent leaks.

Step 3 — Mount Indoor Compressor Section

on a rigid, solid platform or concrete floor. Insert

1/4-in.

asphalt

impregnated

felt

pad

(factory

supplied)

between

unit

basepan

and

mounting

surface to provide full unit support and for vibra­
tion attenuation. (Do not use vibration isolator
under corners of basepan.)

Step 4 — Make Piping Connections — The

38HQ units can be connected to indoor fan coil
using Carrier accessory tubing package or field-

supplied tubing of refrigerant grade. See Tables 1
and 2 (with notes) for unit piping connection type,
size and line size recommendations and Table 4 for
accessory tubing sizes. Maximum allowable system

liquid line length is 100 feet. Maximum vapor line

length from compressor section to indoor coil is 50
feet. Maximum vapor line length from eompressor

section to outdoor coil is 50 feet.

A capacity reduction will result if accessory

tubing is used in 38HQ146 systems. For example,

when a 25-ft, 7/8-in. accessory tubing package is
used, there will be a capacity reduction of 1-1/2%.

For maximum capacity, use 1-1/8 in. vapor line as

recommended in Tables 1 and 2.

When other than 25 ft of interconnecting piping

is used, follow special requirements described in

Refrigerant Charging. Do not use less than 10 ft of

liquid line. Do not cut accessory 7/8-in. vapor line.

Bend or coil to fit.

Do not use damaged or contaminated tubing.

Always evacuate or purge indoor coil, compressor

section and tubing system (use field-supplied refrig­
erant, not unit refrigerant).

When making tubing conneetions, be sure to pro­

vide clearance at unit for electrical connections and

follow tubing isolation method. Step 1, page 3.

Table 4 — Accessories

PART WO

DESCRIPTIOW

38CQ900081

38CQ900111

Honeywell Thermostat and Subbase — Automatic Changeover

Honeywell Thermostat and Subbase — Manual Changeover

38CQ900211

White Rodgers Thermostat and Subbase — Manual Changeover

38CQ900152

Solid State Time Guard 1

24 V (six 38CQ900141)

38HQ900011

Hot Shot Domestic Water Pre-Heater

38CQ900172

38RQ900091

Optimizer Control (six 38CQ900161, ref HH22AQ110)

Optimizer II Control (use with Outdoor Thermostat HH22AG110)

38RQ900032

Outdoor Thermostat — adjustable control for strip heaters, 48-in long Cap Tube

38HÛ900002

Outdoor Thermostat — adjustable control for strip heaters; 36-in long Cap Tube

38RQ900012

38RQ900072

Supplemental Heat Relay (six 38RQ900001 )

Heat Pump Mounting Stand (six 38RQ900061)

38RQ900081

Biflow Liquid Filter-Drier (six KH45LD077)

28VQ900011

Twelve 3/4- x 1-1/8 in Connection Adapters for 38HQ146

TUBING

TUBING PACKAGES

LENGTH

LIQUID LINE

SUCTION LINE

COMPRESSOR

(ft)

OD (in.)

OD (in.)

SECTION 38HQ

38LS934151

15

38LS934201

20

38LS934251

25

38LS934301

30

3/8

3/4

120, 127, 134

38LS934351

35

38LS934401

40

38LS934501

50

38LS978151

15

38LS978201

20

38LS978251

25

38LS978301

30

3/8

7/8*t

140, 146

38LS978351

35

38LS978401

40

38LS978501

50

‘Swaged at each end down to 3/4 i

fCapacity reduction may occur when

nch

7/8-in accessory tubing is used on 38HQ146

5

Advertising