Fig. 7 — Accessory Coupler

Sweat

Connection

to

Compatible

Fitting

(Use

refrigerant grade tubing.)

1. Remove locking nut, rubber O-ring and Schrader

core from valve.

2. Cut tubing to correct length.

3.

Insert tube into Compatible Fitting. Wrap top

and bottom of service valves in wet cloth to

prevent damage by heat. Solder with low-

» temperature (430 F) silver alloy solder.

4. Replace Schrader core.

5.

Evacuate or purge system with field-supplied

refrigerant.

Accessory Flare-to-Compatible Coupler is shown in

Fig. 7. Attach flare nut on coupler to flare fitting on

unit liquid line connection. Connect liquid line to

Compatible

Fitting

using

mechanical

or

sweat

connection. When mechanical connection is made,

use 2 wrenches when tightening Compatible Fitting
nut — one to hold coupler and one to tighten nut.

Liquid line must be flared if coupler is not used.

Step 5 — Make Electrical Connections

Field wiring must comply with local and national

fire, safety and electrical codes. Voltage to units

must be within ± 10% of voltage indicated on
nameplate. Contact local power company for cor­
rection of improper line voltage.

When

making

electrical

connections,

provide

clearance at unit for refrigerant piping connections.

See Table 5 for recommended wire and fuse sizes.

Line and control power wiring for 38HQ outdoor

coil are from connections in the 38HQ compressor

section. Line power wire size to outdoor coil section

must be 14 gage minimum when total wire length

connecting compressor section to coil is under 25

feet. If over 25 ft, use same wire size as compressor

section branch circuit.

INSTALL A BRANCH CIRCUIT DISCONNECT

per NEC of adequate size to handle compressor
section starting current. Provide a separate discon­

nect switch for outdoor coil section. Provide a

separate disconnect per NEC for indoor fan coil and

for each accessory electrie heater circuit as required.

(See Indoor Unit and Electric Heater Installation,

Start-Up

and

Serviee

Instructions.)

Locate

dis-

connect(s) within sight of and readily accessible to

the unit, per section 440-14 of National Electrical
Code (NEC).

BRING

LINE

POWER

LEADS

INTO

COM­

PRESSOR SECTION — Extend leads from dis­

connect per NEC thru 1-1/8in. hole provided in

compressor section top panel (Fig. 2) and into eon-
trol box. Extend line power leads for outdoor eoil
section thru 7/8-in. hole provided in compressor
section top panel and into control box.

Table 5 — Electrical Data (60-Hz)

INDOOR

COMPR

SECTION

OUTDOOR

COIL

V/PH

OPER

VOLTAGE*

COMPR

OFM

FLA

BRANCH CIRCUIT

Min Wire

Size

(AWG)t

Max Ft

Wire

Min Gnd

Wire

Sizef*

Max Fuse or

HACR Type

Ckt Brk Ampstt

MCA

38HQ

Max

Min

LRA

RLA

ICS

OC

ICS

OC

ICS

OC

120

940

65

103

1 5

12

50

20

164

127

940

72

17 1

1 5

10

50

40

22 7

134

940

230/1

254

207

88

20 0

1 5

10

14t

43

25t

10

14t

45

26 7

140

960

94

21 7

2 3

8

58

50

30 7

146

960

106

27 9

2 3

8

50

60

37 2

AWG — American Wire Gage

FLA — Full Load Amps

HACR — Heating, Air Conditioning & Refrigeration
ICS

— Indoor Compressor Section

LRA

— Locked Rotor Amps

MCA — Minimum Circuit Amps

OC

— Outdoor Coil

OFM

— Outdoor Fan Motor

RLA

— Rated Load Amps

‘Permissible limits of the voltage range at which the unit will

operate satisfactorily

fCopper wire sizes based on 60C Use copper or copper-clad

aluminum wire only Use latest NEC for copper-clad aluminum
conductor sizing

^Required when using non-metallic conduit

“Outdoor Coil Wiring — For 25-ft wire run or less, use minimum

14 AWG wire size For longer wire run, use same size wire as

supply to compressor section

ttMaximum dual element size

NOTE All units have 24-v control circuit which requires external
power source