Generac Power Systems 00862-2 User Manual

Page 32

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

INSTALLATION

Section

2 -

Installation

Series QP55-G Recreational Vehicle Generator

2.6.1 ELEgRICAL JUNCTION BOX___________________

Install an approved, square electrical junction box
with a blank cover on the interior or exterior wall of
the area you plan to install the generator (NOT on
the generator). Route the generator’s AC output
leads into this junction box through approved flex­
ible conduit. This is the point of first termination
for generator AC output leads.

2.6.2 WIRING

Wiring should be of stranded copper to reduce

the chance that vibration may cause breakage.

® Wire gauge size should be large enough to handle

at least 1 15 percent of the installed generator's
rated maximum current.

If neutral conductors are used, they must be the

same size as other leg wires.

Route power supply conductors from generator

AC output leads T1 (red). T2 (white), T3 (black)

and the green ground wire through approved
flexible conduit to the electrical junction box on
the compartment wall.

If flexible metal conduit is used between the gener­

ator and the compartment junction box, the con­
duit end that teniiinates the compartment junc­
tion box must be vapor-sealed. Flexible metal con­
duit is NOT vapor tight along its entire length.

• From the junction box, route power supply wares

through approved conduit to either (a) double-pole,

double-throw transfer switch, or (b) approved iso­
lation receptacle. Connecting to a transfer switch
or isolation receptacle must prevent vehicle electri­
cal circuits from being connected to two different
power supplies at the same time (such as genera­
tor and dockside power).

Conductors must be rated

221

°

F (105° C) or

must be of a larger conductor size.

2.6.3 GENERATOR AC

CONNECTIONS

Generator AC output leads T1 (red), T2 (white) and

T3 (black) come out of the generator as shown in

Figure 2.16. Leads T1 (red) and T3 (black) are “hot,”

while T2 (white) is the grounded neutral lead. There

is also a green lead that connects to ground in the

junction box of the recreational vehicle.

Figure 2.16 - Generator AC Output Leads

Line T1 (red) to T2 (white) is protected against over­
load by a 30-amp circuit breaker (CBl). Use this
line-to-neutral

connection

separately

to

operate

120-volt, single-phase, 60 Hertz, AC loads requiring

up to 3,600 watts (3.6 kW) of power. Line T3 (black)
to T2 (white) also is protected against overload by a
20-amp circuit breaker (CB2). IJse this line-to-neu-
tral connection separately to operate similar loads.
However, be sure the total unit load does not
exceed the maximum rating of the generator. The
neutral line (T2, white) on all units is a grounded
neutral.

A

------

Jk

CAUTION Ü-----------

Do NOT

connect

electrical loads in excess of any

circuit breaker rating or you will develop prob­
lems with circuit breaker tripping, which causes a
loss of AC output. Also, do NOT exceed the gen­
erator's rated wattage capacity. Add the watts or
amperes of all lighting, appliance, tool and motor
loads the generator will operate at one time. This

total should be less than the unit's rated
wattage/amperage capacity.

2.6.4 CONDUIT__________________________________

Route the connections between the generator and
the junction box through approved, flexible con­
duit. The following general rules apply:

• Cut wiring to the required length and allow extra

wire for junction box connections.

® Carefully prepare conduit ends to prevent sharp

edges from cutting through wiring insulation.

• Route conduit so it does not interfere with gener­

ator movement.

• If you use metallic conduit, vapor seal the end of

the conduit where it enters the junction box. Do
this

because

flexible

metallic

conduit

is

not

vaporproof along its entire length.

30 Generac* Power Systems, Inc.

Advertising