Ik warning mk – Generac Power Systems 00862-2 User Manual

Page 35

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Section 5 - Post-installation Start-up Adjustments

Series QP55-G Recreational Vehicle Generator

POST-1
INSTALLATION
START-UP
ADJUSTMENTS

3J POST INSTALLATION TESTS

The air-cooled generator set was factoiy tested and

adjusted. You should not be required to adjust the
unit

any

further

except

under

special

circum­

stances.

-------- -ik WARNING

Mk

----------------

A

Do

not

make any unnecessary adjustments.

Factory settings are correct for most applica­

tions. When making adjustments, however, be
careful to avoid overspeeding the engine.

3.2

BEFORE INITIAL START-UP

Before starting, complete the following;

1. Check the engine crankcase oil level and, if nec­

essary, fill to the dipstick “FULL” mark (cross-
hatched area) with the recommended oil. Do not
fill above the FULL mark.
Check the fuel supply. Gas fuel lines must have

been properly purged and leak tested in accor­
dance with applicable fuel codes. All fuel shut­
off valves in the fuel supply lines must be open.

2

.

-A

DANCER

A

If a liquid propane (LP) gas fuel system has

been installed, it must be properly tested for
leaks before operating the system in compli­
ance with ANSI A119.2/NFPA 501C. No leakage
is permitted. You must be sure no gasoline fuel

vapors enter the vehicle interior.

3.3

INITIAL START

When you are absolutely certain that the unit has
been properly Installed and prepared for use, start
the engine as follows;

1. Turn off all electrical loads. Do this by setting

the generator’s main circuit breakers to their

“OFF” (or open) position.

2.

Refer to Part I, Section 2.5, “Starting the

Generator” (Page 8), for cranking and starting
instructions.

The

engine

may

require

more

cranking for initial starting since the fuel lines
have to be primed (use of the primer switch will
shorten this time).

3.

Let the engine warm up for about five minutes

to allow internal temperatures to stabilize.

4.

Carefully inspect the engine/generator for fuel, oil

and exhaust system leaks. Before proceeding to
the next step, correct any leakage immediately.

5.

When all tests and adjustments at no-load are

completed, apply electrical loads and check for
proper operation under load. See Section 3.4.
Run the unit at least 30 minutes with loads
applied.

6.

Turn off all electrical loads by setting the gener­

ator’s main circuit breakers to their “OFF” (or
open) position.

7.

Let the unit run at no-load for a few minutes to

stabilize

internal

engine/

-generator

tempera­

tures. Then, shut down the engine.

NOTE:

The generator set was thoroughly tested and
adjusted at the factory before shipping. No addi­
tional

adjustment

should

be

necessary.

Only

qualified

service

technicians

who

have

been

trained should perform adjustments outlined in
this manual.

3.4

TESTING UNDER LOAD

Apply electrical loads equal to about 75 to 100 per­

cent of the unit's rated wattage/amperage capacity.

Let the unit run at least 30 minutes with load
applied. During this part of the test, check that the
unit is not running excessively hot and that adequate
cooling airflow is available. You must not allow the
unit to overheat during prolonged operation.

NOTE:

The generator engine is equipped with a high
temperature

switch.

The

switch

has

normally

closed (N.C.) contacts. When the engine temper­
ature is too high, switch contacts close, and the

engine shuts down automatically.

GENERAC RECOMMENDS THAT YOU TEST THE
GENERATOR FOR ADEQUATE COOLING.

Generac* Power Systems, Inc. 33

Advertising