Installation – Desa VGL18NRA User Manual

Page 10

Advertising
background image

www.desatech.com

112882-01D

10

Minimum Noncombustible Material
Clearances

If Not Using Mantel

Note:

If using a mantel, proceed to If Using

Mantel. If not using a mantel, follow the informa-

tion below.
You must have noncombustible material(s) above the

fireplace opening. Noncombustible materials (such as

slate, marble, tile, etc.) must be at least 1/2 inch thick.

With sheet metal, you must have noncombustible

material behind it. Noncombustible material must

extend at least 8" up (for all models). If noncombus-

tible material is less than 12", you must install the

fireplace hood accessory (24" and 30" models only).

See Figure 5 for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 12.

Heat Resistant
Material

(A)

Noncombustible

Requirements

Material

for Safe

Distance (A)

Installation

12" or more

Noncombustible
material okay.

Between 8" and 12" Install fireplace hood

accessory (GA6050,
GA6052 or GA6053,
see Accessories,
page 29).

Less than 8"

Noncombustible
material must be
extended to at least
8". See Between 8"
and 12", above. If
you cannot extend
material, you must
operate heater with
flue damper open.

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

INSTALLATION

Continued

If Using Mantel

You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombustible

material must extend at least 8 inches up (for all

models). If noncombustible material is less than

12", you must install the fireplace hood accessory

(24" and 30" models only). Even if noncombustible

material is more than 12", you may need the hood

accessory to deflect heat away from your mantel

shelf. See Figure 5 and Figures 6 and 7 on page 11

for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 12.

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances listed below, you

will need a hood.
Determining Minimum Mantel Clearances
If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6, page 11).
Determining Minimum Mantel Clearances
When Using a Hood
If minimum clearances in Figure 6, page 11 are not

met, you must have a hood. When using a hood

there are still certain minimum mantel clearances

required. Follow minimum clearances shown in

Figure 7, page 11 when using hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirements

of the national product standard.

Follow all minimum clearances

shown in this manual.

Advertising
This manual is related to the following products: