1.2 Applications

Industrial ON/OFF control

External high power relay driving and signal switching

• Laboratory

automation

• Industrial

automation

Switch contact status sensing

Limit switch monitoring

Cooperating with other modules such as A/D and D/A peripherals to
implement a data acquisition and control system

1.3 Specifications


Relay Output

Number of channels: 16

Relay type: SPDT (1 Form C), non-latching

• Switching

capacity:

Max. switching current: 3A

Max. switching voltage: 220V

DC

, 250V

AC

Max. switching power: 50VA, 60W

♦ Max. carrying current: 3A

Failure rate: 10µA

Contact resistance: 150mΩ max.

Relay set/reset time

Operate time: 5ms max.

Release time: 5ms max.

Bounce time: 3ms max.

• Expected

life:

Mechanical life: 10

8

operations min.

Electrical life: 10

6

operations min. (0.4A @ 12V

AC

, resistive load)

Data transfer: Programmed I/O

Auxiliary Digital I/O

Numbers of channel: 8 inputs/outputs

Compatibility: 3.3 V/TTL (5V tolerant)

Data transfers: programmed I/O

Handshaking Signals

• Programmable

polarity

Logic level: 3.3 V/TTL (5V tolerant)

Trigger In source: AUX1, PXI trigger bus, PXI star trigger in

Scanner Advanced destination: AUX0, PXI trigger bus, PXI star trigger
out