Custom Projector Enclosure

8/15/2005

There are five parameters to set for your desired operation. Each is set the same way. On the operators

panel there are four buttons. The left-most button selects the parameter to adjust (will show current

setting). The next button (up arrow) will change the level up, and the next button (down arrow) will

change the level down. The last button (most right) will save the level after adjustment. If you do not

press the SAVE button, then the changes made will be lost. The five parameters are as follows:

Set A/C: Temperature at which the air conditioning will come on. Factory setting is 80 degrees (all

settings in Fahrenheit).

Set Heat: Non-functional in this unit.

Set Alarm Level: Temperature at which the alarm will sound. There is an onboard alarm, which may

be disabled, and a dry contact out to tie into an external alarm system. Factory setting is 110 degrees.

Set Power Level: Temperature at which the switched AC outlet on the power supply will turn off. A

last measure attempt to prevent damage to equipment by turning off power. Factory setting is 120

degrees.

Temperature Readout: Select either Fahrenheit or Celsius. Factory setting is Fahrenheit.

NOTE: BE SURE THE AIR CONDITIONER CONTROL PANEL IS SET TO THE

LOWEST TEMPERATURE SETTING POSSIBLE.