ENMET CP-60 User Manual

Page 10

Advertising
background image

CP-60

ENMET Corporation

7

3.4.2 Relay Contacts

Auxiliary alarms should be powered from an independent power source separate form the instrument power to avoid alarm
failure due to controller malfunction.

Relay are

SPDT

, rated at 10Amp at 110

V

AC

or

10Amp at 30

V

DC

for restive loads, and may be latching or non-latching as

required by the application. They are accessed on the terminals next to each relay see Figures 2 & 5. The contact positions are
noted on the circuit board next to each terminal.

These relay coils are energized when they are in the non-alarm state; the contact conditions given above are for the non-
energized state, which is identical to the alarm state.

In addition, there is a fault relay, which changes state whenever the instrument is in a fault condition. The contact positions are
noted on the circuit board next to each terminal. The coil of this relay is energized when the instrument is in the non-fault state;
the contact conditions given on the circuit board next to the terminal, are for the non-energized state, which is identical to the
fault state.

The PC Board is labeled for the relays in their un-energized state. If the relay is configured for failsafe, then this is also the alarm
condition state. Non-failsafe configured relays in the alarm state, are the reverse of the PC board labeling. Note that the
Fault(FLT) relay cannot be set to operate in a Non-Failsafe mode. Please see the Table 1 below:

Table 1 : Relay Factory Default Failsafe Settings

Factory Default Settings

Position

Failsafe-Alarm

Non-Failsafe-Alarm

Gas Alarm 1

J5

Relay 1 - NO

Normally Open

Normally Closed

Channel 1

J5

Relay 1 - COM

Common

Common

J5

Relay 1 - NC

Normally Closed

Normally Open

Gas Alarm 1

J6

Relay 2 - NO

Normally Open

Normally Closed

Channel 2

J6

Relay 2 - COM

Common

Common

J6

Relay 2 - NC

Normally Closed

Normally Open

Gas Alarm 1

J8

Relay 3 - NO

Normally Open

Normally Closed

Channel 3

J8

Relay 3 - COM

Common

Common

J8

Relay 3 - NC

Normally Closed

Normally Open

Gas Alarm 1

J10

Relay 4 - NO

Normally Open

Normally Closed

Spare

J10

Relay 4 - COM

Common

Common

Not Programmed

J10

Relay 4 - NC

Normally Closed

Normally Open

Gas Alarm 2 System

J14

Relay 5 - NO

Normally Open

Normally Closed

Channel 1 – 3

J14

Relay 5 - COM

Common

Common

J14

Relay 5 - NC

Normally Closed

Normally Open

J15

Relay 6/FLT - NO

Normally Open

N/A

Fault

J15

Relay 6/FLT - COM

Common

N/A

J15

Relay 6/FLT - NC

Normally Closed

N/A

These relay contacts can be used to operate auxiliary alarms or other functions.

3.4.3 4-20mA Outputs

Isolated 4-20 mA outputs are available for data logging or other purposes. An output is supplied for each active channel. These
outputs are available on the Connector 1(

J7

) for channels 1 & 2 and Connector 2(

J4

) for channels 3.

4mA corresponds to the sensor reading of 0 at the bottom of the range.

20mA corresponds to a full scale reading.

Wiring requirements are the same as for the relays.

3.4.4 Digital Outputs

The RS232 & RS485 connections are used for firmware updates and digital communications. The

CP-60

is designed to

operate as a modbus slave. Contact the

ENMET

for further information on wiring for the digital outputs.

Advertising