ENMET CP-60 User Manual

Page 18

Advertising
background image

CP-60

ENMET Corporation

15

5.2.5 Failsafe Configuration

The

CP-60

is factory set in a failsafe configuration. This means that if power is disconnected to the unit, or the relay fails

to properly engage, it fails in such a way that it is in the alarm position.

ENMET

recommends leaving the relay in a failsafe

configuration. However, relay 1 – 5 can be re-configured by using the following procedure.

To change a relay failsafe configuration you must enter the maintenance menu. Press the

OPTION

switch until “Enter Maint

Menu” is displayed then press

SELECT

switch for the Enter Password menu. Enter the valid password as described below.

In the "

Enter Maint Menu

" position

Press the

SELECT

switch "

Enter Password

0

" is displayed. Press

SELECT

switch once, to move cursor to next digit,

this will be the first digit of the password.

In the

000

position, the underline cursor is under the left digit.

Press the

OPTION

switch to change the left digit; select the correct digit.

Press the

SELECT

switch, which locks the digit in place and moves the cursor one digit to the right.

Continue this process until the four-digit password is complete. When a valid password is inserted in this manner, the
display is transferred to the "

Calibration

" portion of the menu. If an invalid password is inserted you are returned to the

Enter Maint Menu display.

After entering a valid password:

Press the

OPTION

switch until “Relay Failsafes” is displayed


Example: Set Relay Failsafe Configuration Flow Chart

5.2.6 Set Output Span Range

To change 4-20 mA output range. This range is set at the factory and should not be changed, contact

ENMET

for information.

Press the

OPTION

switch to continue to next section of maintenance menu.

Press

OPTION

switch until “Exit maint menu” appears and then press

SELECT

switch to return the instrument to the

Operational Display

Example: Set Output Span Flow Chart

O

S

MAINTENANCE MENU

Relay Failsafes

S

O

S

Relay Failsafes

Changes

Failsafe setting from ON to OFF

Continue pressing

S

ELECT

to cycle through all 5 relays

O

Pressing

O

PTION

changes Failsafe setting from ON to OFF

R: 1 Failsafe ON

Relay Failsafes

R: 2 Failsafe

OFF

O

= Press Option

S = Press Select

O

S

MAINTENANCE MENU

mA Output Span

S

O

S

mA OUTPUT SPAN

Changes

digit indicated by underscore cursor

Locks underscored digit and moves cursor to next digit

O

Press

O

PTION

until the channel to be Set is displayed.

Select: CO

mA OUTPUT SPAN

_ 50 CO

S

O = Press Option
S = Press Select

Note:

When in maintenance mode the “_” indicates the location of the cursor, the “

■” block indicates a non-used location.