5 display, 6 operational menu, Figure 7: cp-60 – ENMET CP-60 User Manual

Page 12: Operation menu flow chart 4.7 fault indications

Advertising
background image

CP-60

ENMET Corporation

9

4.5 Display

In clean air a display is shown in Figure 4

.

This position of the display is termed the "operational display". As explained below,

the display can be changed to furnish other information by using the

OPTION

and

SELECT

switches.

4.6 Operational Menu

The operational menu allows the user to:

View alarm set point concentration values

View alarm latching configurations

Enter the maintenance menu with the proper Password.

The operational menu is accessed with the

OPTION

and

SELECT

switches. The operational menu flow chart is shown in

Figure 7,

Pressing the

OPTION

switch is indicated with a "O"

Pressing the

SELECT

switch is indicated with a "S".

If the instrument is left at any location in the operational or maintenance menus, other than the operational display, with no
action taken for a period of 45 seconds, it returns to the operational display.

Figure 7: CP-60

Operation Menu Flow Chart

4.7 Fault Indications

Fault indication occurs:

When a transmitter is not connected to an active channel of the

CP-60

.

When a connected Sensor/Transmitter reading falls out side of its operation parameters (See sensor/transmitter manual).

S

S

O

O

O

S

O = Press Option switch
S = Press Select switch

O

No
Function

O

No
Function

S

S

vL17 A2

v17

vD17

O

No
Function

S

See Maintenance Menu Diagram

O

S

for each active channel

Displays are examples:

✻ – Indicates relay is engaged
Displays are examples of Alarms

Λ

- Indicates alarm triggered on increasing

value of reading

v - Indicates alarm triggered on decreasing

value of reading

Displays are examples of Alarms

L

– Indicates alarm is in latching mode.

Note:

Factory setting for alarms is latching

(no

L

present) – Indicates alarm is in non-

latching mode.

Displays are examples of Alarms

D

– Indicates alarm is in Differential Setting.

(no

D

present) – Indicates alarm is in Standard

Setting.

O

S

No
Function

S

O

No
Function

Alternating

S

O

No
Function

CH-1

CH-3

CH-2

Relays

1 2 3 4 5 6

✻=ON

✻✻✻✻✻✻

CH1 SCALE

(O2)

0.0 – 30.0%

CH2 SCALE (O2)

0.00 – 30.0%

CH3 SCALE

(O2)

0.0 – 30.0 %

vL19.5 A1 vL19.5

vD 19.5

ALARM1 Delays

(Seconds)

30 mASPAN 30.0
30

5

5

5

5

Enter Password

_

Enter Maint Menu