ENMET CP-60 User Manual

Page 17

Advertising
background image

CP-60

ENMET Corporation

14

5.2.3 Set Alarm “Delay On”

The alarms may be set to delay activation by 1 second increments, from 1 to 30 seconds.

W

ARNING

:

Extended alarm delays may cause operational failures, injury or death.

Factory set default value is 5 seconds.

After entering a valid password:

Press the

OPTION

switch until;

“Maintenance Menu Set Alarm Delay”

appears on display.

Press the

SELECT

switch, "

ALARM Delay Select: O2

" is displayed.

Press the

SELECT

switch; "

ALARM Delay =

005

" is displayed, with the underscore cursor under the left position.

Press the

SELECT

switch to move the cursor and the

OPTION

switch to lock in the correct digit and move the cursor one

digit to the right. Press the

SELECT

switch when the last digit is accepted display returns to the "

Set Alarm Delay

"

position.

Press the

OPTION

switch to continue on to the Set New Password section

Example: Set Alarm Delay Flow Chart

5.2.4 Relay Configuration

To change a relay configuration you must enter the maintenance menu. Press the

OPTION

switch until “Enter Maint Menu” is

displayed then press

SELECT

switch for the Enter Password menu. Enter the valid password as described below.

In the "

Enter Maint Menu

" position

Press the

SELECT

switch "

Enter Password

0

" is displayed. Press

SELECT

switch once, to move cursor to next digit,

this will be the first digit of the password.

In the

000

position, the underline cursor is under the left digit.

Press the

OPTION

switch to change the left digit; select the correct digit.

Press the

SELECT

switch, which locks the digit in place and moves the cursor one digit to the right.

Continue this process until the four-digit password is complete. When a valid password is inserted in this manner, the
display is transferred to the "

Calibration

" portion of the menu. If an invalid password is inserted you are returned to the

Enter Maint Menu display.

After entering a valid password:

Press the

OPTION

switch until “Configure Alarms” is displayed

L

= Low Alarm = Alarm 1,

H

= High Alarm = Alarm 2,

B

= Both Alarms, = No Relay linked to channel

Example: Set Relay Configuration Flow Chart

The Table 2 below shows the default relay links for 3 channel system.

Table 2: Default Relay Links

Channel 1

Channel 2

Channel 3

Channel 4

Relay 1

Low Alarm

Channel 4 Not
Available in CP-60
Default
programming of
circuit only

Relay 2

Low Alarm

Relay 3

Low Alarm

Relay 4

Spare

Spare

Spare

Relay 5

High Alarm

High Alarm

High Alarm

Relays can be linked to specific alarms.

N

OTE

:

Each operating channel must be linked to at least 1 relay.

O

S

MAINTENANCE MENU

Set Alarm Delays

S

O

S

Alarm Delay -

Changes digit indicated by underscore cursor

Locks underscored digit and moves cursor to next digit

O

Press Option until the channel to be Set is displayed

Select: XX

Alarm Delay -

0000

O

= Press Option

S =

Press Select

Note:

When in maintenance mode the “_” indicates the location of the cursor, the “

■” block indicates a non-used location.

O

S

MAINTENANCE MENU

Configure Alarms

S

O

S

Ch 1,2,3

Changes digit indicated by underscore cursor

Locks underscored digit and moves cursor to next digit

O

Press Option changes letter indicated by underscore cursor

R1 L

Ch 1 2 3

R2 L

!