ENMET CP-60 User Manual

Page 15

Advertising
background image

CP-60

ENMET Corporation

12

5.2.2 Set Alarm Points

Factory alarm set points are discussed in Section 4.2, See Table 1. To change the alarm points, you must enter the maintenance
menu.

N

OTE

:

Changing the alarm points on the

CP-60

will NOT change the alarm points on the sensor transmitter.

Entrance to the maintenance menu is guarded with a four-digit Password. The factory default setting of the password is 1270.
When a valid numerical password is inserted, the user is allowed to enter the maintenance menu.

In the "

Enter Maint Menu

" position

Press the

SELECT

switch "

Enter Password

0

" is displayed. Press

SELECT

switch once, to move cursor to next digit, this

will be the first digit of the password.

In the

000

position, the underline cursor is under the left digit.

Press the

OPTION

switch to change the left digit; select the correct digit.

Press the

SELECT

switch, which locks the digit in place and moves the cursor one digit to the right.

Continue this process until the four-digit password is complete. When a valid password is inserted in this manner, the display is
transferred to the "

Calibration

" portion of the menu. If an invalid password is inserted you are returned to the Enter Maint

Menu display.

After entering a valid password

:

Press the

OPTION

switch until;

“Maintenance Menu Set Alarm1”

appears on display.

Press the

SELECT

switch, "

ALARM1 Select: O2

" example is displayed.

Press the

SELECT

switch; "

ALARM 1

V

" is displayed, with the indicator flashing,

Λ

for

ascending trigger point or

V

for descending trigger point indicator.

Press the

OPTION

switch to toggle between

Λ

and

V

; select the correct indicator.

Press the

SELECT

switch to lock in the correct indicator. "

ALARM 1

STD

" is displayed

Press the

OPTION

switch to toggle between STD and

DIFF; select the correct indicator.

Press the

SELECT

switch to lock in the correct indicator.

IF:

STD is selected, "

ALARM 1

V

L

" is displayed.

The next character is the latching indicator

L

or

NO

L

press the

OPTION

switch to toggle the latching mode.

The next characters are the alarm 1 value, press the

OPTION

switch to select each digit of the value

When the last digit is accepted display returns to the Maintenance Menu "

Set Alarm1

" position.

IF:

DIFF is selected, "

ALARM 1

V DIFF 19.5

" is displayed, Factory default setting.

The next characters are the alarm 1 value, press the

OPTION

switch to select each digit of the value

Move the cursor to the first digit and, Press the

SELECT

switch to lock in the correct character and move the cursor to the

right.

"

ALARM 1

DIFF BAND 0.0

" is displayed, to set alarm 1 differential. With

SELECT

switch move cursor to left.

Press the

OPTION

switch to select each digit of the value.

Note:

The Alarm 1 differential value is the delay of the

CP-60

staying in alarm condition until after the measured reading has

returned past the alarm point by the differential value. Example: If the alarm set point is

V

19.5 and the differential is 2, the

CP-60

will go into alarm at 19.5 and stay in alarm until the reading has risen above 21.5.

Repeat the above procedure for each sensor alarm 1 to be changed.

Press the

OPTION

switch to move to alarm 2, "

Set ALARM2

" is displayed.

Repeat as for alarm 1 using the

STD

section. Alarm Diff is not available for Alarm 2.

Press

OPTION

switch until “Exit maint menu” appears, then press

SELECT

switch to return the instrument to the Operational

Display

Note:

When in maintenance mode the “_”

indicates the location of the cursor, the

■” block indicates a non-used location.