INSTALLATION

If you are using the cylinder with a gasfired boiler as per GB

standards, you may have to install a suitable heating pump in the

reheating circuit.

9.4.1

Installing the 2-way motorised valve

1

The 2-way motorised valve prevents the cylinder from

overheating.

Install the 2-way motorised valve (1) supplied with the cylinder in

the supply line of the gas-fired boiler. Do not install the valve with

the head upside down.

9.5

Installing hot water pipes

Connect the hot water piping to the 22 mm hot water connection

of the cylinder.

Lay the 22 mm piping up to the first T-piece.

The required diameter of subsequent pipes depends on the

system design.

9.5.1

Connecting up the secondary circulation line

The cylinder has a connection with a 15 mm diameter for a

circulation line.

• Connect a WRAS-approved circulation pump which has a non-

return valve with the circulation connection.

• Establish the connection to the circulation line.

If you are not using the secondary circulation

connection, you must ensure that it is properly closed

off. Where secondary return circuits are used, an

additional expansion vessel may be required.

1

AB

B

A

Key:

1 Thermostat mixer

a Hot water

b Cold water

ab Mixed water

In a thermal solar system, a hot water thermostat mixer must

be installed as scald protection. The hot water thermostat mixer

mixes the hot water from the cylinder with cold water to produce

water with a maximum temperature of between 30 and 60 ºC as

required.

The hot water thermostat mixer must be provided by the installer.

9.5.2

Installing the hot water thermostat mixer (with

secondary circulation line)

230

2

7

10

1

1

6 5

9

3

4

8

Key:

1 Non-return valve

2 Hot water thermostat mixer

3 solar controller

4 Hot water pipe

5 Circulation line

6 Circulation pump

7 Contact thermostat

8 expansion relief valve

9 Cold water pipe

10 solar cylinder

Where possible, avoid installing a circulation line, since a

circulation line results in higher energy consumption.

If the installation of a circulation line is required, keep circulation

operations to a minimum by only using circulation mode when

required for demand and temperature reasons.

Connect the circulation line (6) to the hot water pipe (4) via a hot

water thermostat mixer (2).

9.6

Installation of cold water pipe

The efficiency of an unvented cylinder depends on the available

pressure in the cold water pipe and the flow rate. To obtain

maximum cylinder efficiency, there must be a suitable cold water

pipe, i.e. the measured static line pressure must be at least 2.0

bar. A corresponding flow rate of at least 20 - 25 l/min must be

available.

The pressure in the cold water pipe will be reduced

at times of high consumption. Thus, measurements

should be taken at such times.

The cylinder still works satisfactorily with a pressure below 2 bar

but the flow rate is reduced. If the pressure is below 1 bar, you

should not install an unvented cylinder.

Glow-worm can provide information on alternative hot water

supply systems.