INSTALLATION

- 12 -

4.2 Flue confi guration description

4.2.1 Horizontal concentric fl ue Ø 60/100 mm
or Ø 80/125 mm (C13 type installation)

a

If the terminal is at less than 1.80 m from the
ground, you must install a terminal protection kit.

Ø 60/100 mm

L

63

1

Key
1 Gasket (fi tted)

Ø 80/125 mm

L

1

Key
1 Gasket (fi tted)

Type

Max length

Ø 60/100

8 m

Ø 80/125

20 m

Type

Max length

Ø 60/100

512 mm

4.2.3 Vertical concentric fl ue Ø 60/100 mm
or Ø 80/125 mm (C33 type installation)

a

If the terminal is at less than 1.80 m from the
ground, you must install a terminal protection kit.

L

Type

Max length (L)

Ø 60/100

8 m

Ø 80/125

20 m

Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m.

L

Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m.