INSTALLATION

- 15 -

• Where possible keep the existing boiler/circulating pump in

place when fl ushing the system

5.6.2 Flushing the system

• Fill the system with cold water and check for leaks.

• Open all drain cocks and drain the system.

• Close drain cocks and add a suitable fl ushing agent (cleaner)

compatible with Aluminium at the correct strength for the
system conditions in accordance with the manufacturer’s
instructions.

Examples of suitable fl ushing agents/cleansers are:
Sentinel X300, X400
Fernox F3

• Circulate

the

fl ushing agent before the boiler is fi red up.

• Run the boiler/system at normal operating temperature as

directed by the manufacturer of the fl ushing agent.

• It is essential to drain and thoroughly fl ush the whole system

to remove the fl ushing agent and debris.

• It may be necessary to use a power fl ushing machine to aid

the cleansing procedure in some circumstances.

• Close the drain cocks and refi ll with fresh water and a

suitable inhibitor.

• Vent any air from the boiler and system.

5.6.3 Inhibiting the system

Add a suitable inhibitor or combined inhibitor/anti-freeze, if the
system is exposed to freezing conditions, to the heating system
in accordance with the DWTA code of practice and inhibitor
manufacturer’s guidelines.

Examples of suitable inhibitors are:
Sentinel X100
Fernox protector F1

Artifi cially softened water must not be used to
fi ll the central heating system.

Sealing agents - The addition of sealing agents
to the system water is not permitted as this can
cause problems with deposits left in the heat
exchanger.