Installation – Glow-worm Flue User Manual

Page 22

Advertising
background image

0020095198_02 - 06/11 - Glow-worm

INSTALLATION

- 22 -

6.8

Termination above eaves

The Horizontal termination should be terminated 100mm

above the eaves. The vertical flue outlet should be a minimum

distance of 300mm above the eaves.

Exposed site conditions may require that the flue be secured as

described in diagram.

6.9

Termination

The termination can be changed from 87° horizontal to 45° or

vertical.

To achieve this remove the wire bird protection guard from the

87° Bend. Remove the O-ring seal from the 1M Pipe or 45°

elbow and fit the wire bird protection guard into the 1M Pipe or

45° elbow where the O-ring seal was fitted.

It is not necessary to fit a terminal guard over the appliance

main flue outlet. However should the plume management kit

terminal discharge in a place where it requires protection, a

guard should be fitted.

Vertical

Terminal

45°Terminal

Wall plate

Stud bolt

Pipe fixing bracket

IMPORTANT:

Remove the seal and fit the

bird protection wire from the

87° bird protection bend

Bird protection

wire

Seal

Minimum

Clearance

Vertical 300mm

90

0

or 45

0

100mm

90°Terminal

(supplied)

WE RECOMMEND THAT

TERMINALS ABOVE

EAVES ARE SECURED

6.10 fixing Instructions

These instructions are supplied to enable the flue pipe from the

Plume Management Assembly to be securely fixed either at the

eaves or on the gable end of a building when the flue terminal is

to be terminated above the roof.

The stud bolt and wall plate fixings can be obtained from kit pt.

no. A2043900 and used with the pipe fixing bracket supplied.