5 electrical wiring – Glow-worm 56/3e Back Boiler User Manual

Page 15

Advertising
background image

15

221725B

Ls

b

N

230V~50Hz
MAINS
SUPPLY

br - brown
b

- blue

g/y - green/yellow
SL - switched live

KEY

g/y

SL

br

Diagram 5.4

Diagram 5.5

6203

7884

MAINS
SUPPLY
PLUG

CONTROL
BOX

5.3 Boiler Control Box

Taking care that the POWER IS OFF, wire the incoming mains
cable to the mains plug supplied in the fittings pack. Do not
connect the mains supply plug to the control box socket, see
diagram 5.5.

NOTE: The ignition sequence is fully automatic and will
commence when mains voltage is applied.

5.4 Testing - Electrical

Checks to ensure electrical safety must be carried out by a
competent person.

After installation of the system, preliminary electrical system
checks as below should be carried out,

1. Test insulation resistance to earth of mains cable.

2. Test the earth continuity and short circuit of all cables.

3. Test the polarity of the mains.

4. With the mains supply off. Plug the mains supply plug into the
control box socket, see diagram 5.5.

5.5 Overheat cut-off device (sealed systems
only).

A Kit No. 459033 is available with fitting instructions.

5 Electrical Wiring

LEFT HAND CLIPPING POSITIONS A and B

RIGHT HAND CLIPPING POSITIONS C and D

OVERHEAT
CUT-OFF
DEVICE

CONTROL THERMOSTAT
PHIAL

A

B

C

D

RETAINING
PIN

C