8 Servicing

Servicing Notes

a) To ensure the continued efficient and safe operation

of the appliance it is recommended that it is checked
and serviced as necessary at regular intervals. The
frequency of the servicing will depend upon the
particular installation conditions and usage, but in
general once a year should be enough.

b) It is the Law that servicing must be carried out by a

competent person.

c) Remove the fire front

d) Refer to the Gas Fire Front Installation and Servicing

Instructions for full details of fire front removal.

e) After completing any servicing always test for gas

soundness with a suitable leak detection fluid and
carry out functional check on controls.

f) Unless stated otherwise reassembly of all components

is in the reverse order to that for removal.

g) The Flue Blockage Safety Device MUST NOT be adjusted
or disconnected. If replacing use only the correct and approved
part.

8.1 Isolation of Services

Isolate the electrical supply to the back boiler.

With the fire front removed.

Refer to diagram 6.1 to identify the controls.

Turn control thermostat knob “A” anti-clockwise to “0” “Off”
position.

Turn appliance gas service cock to “Off”, see diagram 4.12.

8.2 Sensing Tube Assembly.

Remove the combustion chamber extension, see diagram 4.5.
Unclip the mains supply cable if required.

Remove spigot duct, see diagram 8.10.

Remove the sensing tube bracket securing screw, carefully pull
the sensing tube assembly away from the sensing tube fitting on
the draught diverter assembly and from the combustion products
discharge safety device.

Clean or replace the lint arrester, see diagram 8.1.

Remove the sensing tube fitting and the tubing nut to access the
internal filter.

Clean or replace the internal filter, check the “O” rings for
damage, replace if necessary, see diagram 8.1.

IMPORTANT NOTE: When replacing the sensing tube check
the “O” rings, internal filter and lint arrester are fitted.

8.3 Gas Controls Assembly and Burner.

Remove the control box, hold with both hands squeeze tilt
forward and unhook, see diagram 8.3.

Turn the box over.

Disconnect the ignition lead from the control board and remove
by threading it through the grommet in the rear of the control
box, see diagram 10.6.

Disconnect the mains electrical plug from the control box, see
diagram 8.2.

Disconnect the union at the gas service cock, support with a
spanner see diagram 4.12.

Remove the thermostat phial and overheat cut-off device phial
if fitted (sealed systems only), from the phial pockets, unclip the
capillary tubes, see diagram 5.4.

Diagram 8.1

6851

INTERNAL
FILTER

SENSING
TUBE FITTING

BRACKET
SECURING
SCREW

SENSING TUBE

“O” RINGS

SENSING
TUBE

DRAUGHT
DIVERTER

FLUE
BLOCKAGE
SAFETY DEVICE

TUBING
NUT

RETAINING
NUT

LINT
ARRESTER

RETAINING
CLIP

Remove the four combustion chamber securing screws.

Pull the gas control valve forward releasing it from the retaining
pin, see diagram 8.4.

Slide the control/burner assembly forwards and up to remove,
see diagram 8.2.